energy savings at little-to-no additional capital cost.
These roadmaps outline what is achievable utilizing
current codes and standards, and represent a starting
point for NZE or NZE-ready hospital design. Insights
from recently built hospitals also showcase that lower
energy hospitals are possible. For example, the Swedish
Issaquah Hospital in the U.S. Pacific Northwest.
operates below 120 KBtu/SF-yr (380 kWh/m²-yr),
and the Peace Island Medical Center operates under
100 KBtu/SF-yr (315 kWh/m²-yr). International
examples show that there is consistent achievement of
similar or better results (11).
The major points for Targeting 100!, the AEDG, and
recent built examples include:
1. Hospitals are large energy consumers for somewhat
surprising reasons: Minimum requirements for
ventilation mean that a large portion of the energy
consumed in a hospital is being used to transport
and condition ventilation air. Re-heat energy is the
single largest energy consumer, representing 40-50%
of the total energy consumed in a typical facility.
Hospitals’ internal requirements dictate that air be
very cool in some hospital areas; spaces needing the
coolest air (such as surgery suites) determine the
air temperature traveling through an entire zone.
All spaces needing warmer air (e.g. offices, exam
rooms, patient rooms) require air to be re-heated
at the delivery point. Additionally, hospitals are
densely occupied, operate 24 hours per day, seven
days a week, and house a lot of energy consuming
equipment.
2. To reach low energy targets, designs should:
a. Prioritize Load Reduction through Archi-
tectural Systems. Energy reductions start by
aggressively reducing external climate dependent
loads and activity dependent internal loads. A
simultaneous focus on peak loads and whole
building annual energy loads is important for
solving the energy and cost equation. Smaller
peak loads mean smaller plant equipment which
translates to lower capital cost investments;
lower overall load profiles provide flexibility in
ventilation system choice and mean significantly
reduced annual energy use profiles for heating
and cooling, and thereby, annualized energy
savings. Highly coordinated architectural and
building mechanical systems are required to meet
large load reduction goals. For example, exterior
shading on the envelope significantly reduces
solar heat gain enabling a de-coupled approach
to building heating, cooling, and ventilation
systems. De-coupling heating and cooling from
ventilation of rooms enables much lower whole
building load profiles and significantly reduced
peak loads.
b. Re-Heat Energy Reduction through Building
Mechanical Systems. Strategies for reducing or
eliminating re-heat include de-coupling space
tempering and ventilation for most spaces; fluid
rather than air-transport of heat and cooling for
peak conditions; and the final distribution of
heating and cooling to each space via a bundle of
de-coupled systems such as radiant heating and
cooling panels. These systems require a limited
load profile and thus, require prioritizing load
reduction strategies. Optimized heat recovery
from space heat and large internal equipment
sources also reduces the overall energy demand
as does including advanced HVAC and lighting
controls: turn off what is not in use.
c. Efficient Plant-Level Equipment. Provide the
ability to capture heat in the most efficient way.
Utilize advanced heat recovery at the central
plant and implement heat pumping, or enhanced
heat recovery chillers paired with highly efficient
boilers.
Implication for on-site energy
production
Targeting 100!, the AEDG for Large Hospitals, and
recent built examples show that achieving an Energy Use
index (EUI) of 100 KBtu/SF-yr is possible alongside
current codes and standards. Even though these exam-
ples utilize significantly less energy than their typical
counterparts, they still use too much energy to achieve
NZE by simply adding renewables. The total energy use
for a 250,000 SF hospital operating at 100 KBtu/SF-yr
would require a 6850 kW photovoltaic array, meas-
uring nearly 500,000 SF (in Seattle, WA, U.S.), or a
slightly smaller, 4500 kW, 300,000 SF of PV array (in
sunnier Los Angeles, U.S.) to produce enough energy to
offset the total energy demand in an average year (12).
The site area size and cost of PV equipment is not real-
istic to achieve NZE. If these examples reduced their
energy demand to 50 KBtu/SF-yr (158 kWh/m²-yr),
that implies a much smaller array, 3400 kW (Seattle) or
2250 kW (Los Angeles), using just under 250,000 SF
and 160,000 SF respectively (13). An even lower EUI,
more efficient array, or sunnier climate would imply an
even smaller and more affordable array to achieve NZE.
These calculations highlight that in order to approach
NZE, or become NZE ready, a hospital must reduce
its energy footprint significantly beyond what has been
achieved to date in the U.S.
REHVA Journal – October 2017 33
Articles