Ozone Systems
Installation & Operation Manual
CD1500 • CD2000
Corona Discharge Ozone Generators
Tested and certified by
WQA to NSF/ANSI 50 as a
component only.
ClearWater Tech, LLC.
Integrated Ozone Systems
850-E Capitolio Way, San Luis Obispo, Ca 93401 • 805-549-9724 • Fax: 805-549-0306 • E-mail: [email protected] • www.cwtozone.com
Copyright © 2011 - ClearWater Tech, LLC • Reproduction of any kind is prohibited • LIT515 • Rev 092111
-1-
O
O
3
3
INTRODUCTION
This Installation and Operation Manual is
written to assist in the installation, operation
and maintenance of ozone delivery systems
manufactured by ClearWater Tech, LLC.
This equipment has been designed using the
most modern materials and technology
available.
Please read this manual carefully and in its
entirety before proceeding with any
installation, operation or maintenance
procedure associated with this equipment.
Failure to follow these instructions could
result in personal injury, damage to the
equipment or reduced product performance.
In an ongoing effort to improve reliability and
operating efficiency, ClearWater Tech may find it
necessary to make changes to its products.
Therefore, the information contained in this
manual may not conform in every respect to
earlier versions of ClearWater Tech ozone system
found in the field. If you have any questions,
please contact your ClearWater Tech dealer or the
ClearWater Tech service department.
-2-
TABLE OF CONTENTS
Overview ......................................................................................................................... 3
Safety Information ......................................................................................................... 4
Theory of Operation/Product Description.................................................................... 6
Figure 1 – Complete Ozone System............................................................................. 6
Installation Procedures – Getting Started .................................................................... 8
Installation Procedures Plumbing .............................................................................. 9
Figure 2 – Sidestream Plumbing Installation Diagram ............................................. 11
Figure 3 – Full Flow Plumbing Installation Diagram ............................................... 11
Figure 4 – Contact Column Installation Diagram ..................................................... 12
Figure 5 – Contact Column Exploded View .............................................................. 12
Installation Procedures – Electrical ............................................................................ 13
Figure 6 – External Loop Electrical Interface........................................................... 14
Installation Procedures – Pneumatic .......................................................................... 15
Figure 7 – Typical Pneumatic Hookup ...................................................................... 15
Figure 8 – Typical Oxygen Concentrator Detail ....................................................... 16
Figure 9 – Vacuum Break Detail............................................................................... 17
Start-Up and Calibration............................................................................................. 18
Figure 10 – Pneumatic Operation Parameters.......................................................... 20
Maintenance ................................................................................................................. 21
Figure 11 – CD15nx and CD30nx High Output Drive Module.................................. 23
Figure 12 – Ozone Generator Cooling Fan Assembly ............................................... 23
Figure 13 – 2” Reaction Chamber – Exploded View ................................................. 26
Troubleshooting ........................................................................................................... 27
Appendix A – Specifications ........................................................................................ 31
Appendix B – Parts List............................................................................................... 34
Appendix C – Maintenance Kit ................................................................................... 35
Appendix D – Logic Schematics .................................................................................. 36
Appendix E – Drive Module Input Voltages............................................................... 38
Appendix F – Warranty Information.......................................................................... 39
-3-
O
2
+
Electrical
Field
O
1
=
O
3
O
2
+
O
1
=
O
3
Ozone (O
2
)
OVERVIEW
How Ozone In Generated
Ozone is generated by exposing oxygen molecules (O
2
)
in an air stream to a controlled, high energy electrical
field. As the air stream passes through the electrical
field produced inside the ozone generator, some oxygen
molecules are split, forming single oxygen atoms (O
1
).
These oxygen atoms then recombine with other oxygen
molecules in the air stream, forming ozone (O
3
)
Properties of Ozone
Ozone is the most powerful oxidizer available that can be safely used in water treatment
1
. It is used to treat
drinking water, bottled water, swimming pool water, waste water, food and beverage processing water, and in
many other applications. Ozone is effective in performing the following:
Disinfection Bacterial disinfection,
inactivation of viruses and cysts.
Oxidation of Inorganics Precipitates, iron,
manganese, sulfides nitrides and organically-
bound heavy metals
Oxidation of Organics Including organics
causing color, taste, and odor problems. Some
detergents and pesticides, phenols, VOCs,
turbidity control and micro-floccuity control and
micro-flocculation of soluble organics.
Benefits of Ozone Use
Ozone is generated on site no transportation or storage is required
The most powerful oxidizer commercially available very effective for
disinfection and oxidation without handling problems.
Ozone creates no potentially harmful by-products (such as THMs) the only by-
product is oxygen.
Ozone leaves no telltale taste or odor.
1
Water Quality Association, “Ozone for POU, POE and Small Water System Water Treatment Applications,” Lisle, IL, 1999
Molecular Weight
48
Odor
Readily detectable at concentrations
above 0.02 ppm in air
Color
Bluish in ozone generator cell, but
ozone/air mixture exiting generator is
invisible even at high ozone
concentrations.
Gas Density:
2.144 grams/liter at 32°F
(Approximately 150% that of oxygen).
Solubility
Only partially soluble in water, but
about 10-20 times more soluble than
oxygen (at 68°F).
-4-
Safety Information
Safety Warnings
Two aspects of ClearWater Tech ozone generators represent potential dangers ozone gas and high voltage
electricity.
OZONE GAS WARNING: HIGH CONCENTRATIONS OF OZONE GAS ARE
DANGEROUS TO HUMANS. LOW CONCENTRATIONS CAN
CAUSE IRRITATION TO THE EYES, THROAT AND
RESPIRATORY SYSTEM.
This ClearWater Tech corona discharge ozone generator
is designed to produce highly concentrated ozone.
While safety precautions have been taken, entering the
equipment area should be avoided if ozone gas is
detected. Ozone has a very distinctive odor and is
detectable at very low concentrations (0.02 ppm), which
is far below OSHA’s maximum permissible exposure
level of 0.1 ppm.
HIGH VOLTAGE WARNING: CLEARWATER TECH OZONE GENERATORS
OPERATE AT HIGH VOLTAGE. DO NOT TAMPER WITH
OR DELIBERATELY BYPASS THE COVER OR SAFETY
SWITCHES BUILT INTO THE OZONE GENERATOR
UNLESS INSTRUCTED TO DO SO BY THIS MANUAL. IF
CONTACT IS MADE WITH OPERATING HIGH VOLTAGE
COMPONENTS, ELECTRIC SHOCK WILL OCCUR.
ClearWater Tech corona discharge ozone generators take line voltage and convert it to 48 VDC. A high voltage
transformer then boosts the voltage. Proper care must be used by a qualified electrician when making any internal
adjustments or performing any maintenance procedures.
Safety Information
-5-
IMPORTANT SAFETY INSTRUCTIONS
When installing and using this electrical equipment, basic safety precautions should always be followed,
including the following:
1. READ AND FOLLOW ALL INSTRUCTIONS.
2. SAVE THESE INSTRUCTIONS.
3. All electrical connections should be made by a licensed, qualified electrician.
4. Before attempting any electrical connections, be sure all power is off at the main circuit breaker.
5. Install all electrical equipment at least five feet from any open body of water using non-metallic plumbing.
6. Install check valves and a vacuum break to prevent water from contacting the electrical equipment.
7. The electrical supply for this product must include a suitably rated switch or circuit breaker to open all
ungrounded supply conductors to comply with Section 422-20 of the National Electrical Code, ANSI/NFPA
70-1987. The disconnecting means must be readily accessible to the operator(s) but installed at least five
feet from any open body of water.
8. Be sure to bond (ground) the system using the copper-bonding lug on the bottom of the ozone generator.
The system should be bonded with solid copper wire conforming to all local, state and national electrical
codes.
9. The system should be sized appropriately for its intended use by a qualified professional familiar with the
application. This equipment must be validated by the manufacturer for its intended use; failure to do so
may void the warranty.
-6-
Theory of Operation/Product Description
ClearWater Tech ozone systems are designed for safe, effective use in a variety of water treatment applications.
The CD1500 and CD2000 ozone generators may be part of a larger integrated ozone system. Such a system may
include the following components required for reliable, efficient ozone production and can be divided into four
general segments:
Complete Ozone System
Figure 1
Air preparation system Ozone generator Ozone injection/contacting Ozone destruct
SHOWN: CLEARWATER TECH CD2000 OZONE SYSTEM
Air Preparation System
ClearWater Tech ozone generators require a source of clean, dry, oil-free, oxygen-enriched air for effective ozone
production. To meet that need, ClearWater Tech employs pressure swing adsorption (PSA) technology with an
oil-less compressor to increase the concentration of oxygen and reduce the moisture content in the feed gas (the
air supplied to the ozone generator). This substantially improves the output capability of the ozone generator and
prevents premature failure of key internal components. These air preparation systems deliver 90%+/-3% oxygen
purity at -60°F dew point and at very low pneumatic pressures, minimizing noise and reducing compressor wear.
If “Plant Air” feed gas is to be used in place of the ClearWater Tech air preparation system, the same air quality
standards must be met to achieve the ozone output and longevity of the ozone generator. In addition to oil and
water coalescent filters, a pounds per square inch (PSI) regulator must be installed when using plant air feed gas.
This regulator must be set to a maximum of 10 PSI.
Ozone Generator
ClearWater Tech ozone generators are designed to supply high concentrations of ozone gas. The oxygen feed gas
produced by the air preparation system is supplied to the ozone generator. The vacuum created a the ozone
injector draws the ozone gas created by the ozone generator into the water line.
As the feed gas enters the fused, thermally protected reaction chambers inside the ozone generator, some of the
oxygen molecules are split while passing through the high voltage electrical field (the “corona”), forming single
Booster Pump
Ozone Injector
Water Flow
Air Preparation
System
Ozone Generator
Vacuum
Break
Contact Vessel
Ball
Valve
Water
Trap
Ozone
Destruct
Unit
Off Gas
Vent
OPTIONAL DESTRUCT SYSTEM
-7-
oxygen atoms (O
1
). These oxygen atoms then recombine with other oxygen molecules in the air stream, forming
ozone. The modular, multiple reaction chamber design in the CD2000 allows the ozone generator to keep working
even if one of the chambers requires service.
Depending on the application, the ClearWater Tech ozone generator may be interlocked with an ORP controller,
PPM controller, pressure switch, timer or circulation pump. Other safety features are also built in, including
thermal protection.
Ozone Injection/Contacting
The ozone injector serves two purposes: One, it creates
the vacuum required to safely draw the ozone gas from
the ozone generator and two, it provides a means by
which the ozone gas can become dissolved in water. A
very dynamic injection process is required to
effectively dissolve ozone in water.
ClearWater Tech injection systems use only Mazzei®
injectors for maximum mass transfer efficiency. The
injector produces a cavitation effect, enabling the ozone
gas to join the water stream in the form of extremely
tiny bubbles. Lots of tiny bubbles increase the surface
area of the ozone thus increases the amount of area
available to ozonate the surrounding water.
Depending on the application and the water treatment goals, a ClearWater Tech contacting system may also be
required. Some oxidation reactions take place so quickly that they are limited only by the rate at which the ozone
is dissolved in the water. Other reactions, such as disinfection, may require that proper ozone residual be
maintained for a specific amount of time. A correctly-sized contact vessel is used for this purpose.
Ozone Destruct
The ClearWater Tech off-gas destruct system consists of two components: the ozone destruct unit (a heated
chamber filled with manganese dioxide and copper oxide) and a water trap. Used in conjunction with a
ClearWater Tech off-gas vent, the ozone destruct system is an effective way to vent the contact vessel(s) when it
is impractical to send the off-gas to atmosphere or reintroduce it to the water.
A Short Course in Fine Bubbles
Lesson 1 The large bubble (20mm) has a
volume of 4.19 cm3 and a surface area of
12.6 cm2.
Lesson 2 296small bubbles (3mm) could be
made from the large bubble in lesson 1. They
would have a total surface area of 83.6cm2. This
is 6.6 times the surface a CD1500 • CD2000rea
of the large bubble.
Lesson 3 Theoretically, 6.6 times as much
water could be ozonated with the same
amount of ozone!
-8-
Installation Procedures – Getting Started
Unpacking
Compare the ozone system equipment received to the packing list provided.
Before beginning any installation procedures, thoroughly inspect all components
for damage. If damage is noticed, promptly notify the freight carrier and request
an on-site inspection. Inspect all packing materials for small parts before
discarding. Inspect all plumbing, fittings and tubing for packing material that
may have become lodged in openings.
Equipment Placement
When placing the ozone system components in the equipment room, make sure to consider safety, maintenance
requirements, local building and fire codes, etc. The components should be easily accessible by the operators,
including equipment access doors and electrical hook-up boxes. All meters, gauges, indicator lights, and switches
should be visible and accessible. Dimensional drawings of each air preparation system and ozone generator are
included in Section A of the Appendix.
The air preparation system and ozone generator should be located as close as possible to the point of ozone
injection. Ozone is an unstable gas and will begin reverting back to oxygen very quickly. To determine the most
favorable ozone injection point, the following items should be considered:
Located downstream of all other existing water system components.
Located upstream of the residual sanitizer injection point (if so equipped).
In a Sidestream plumbing configuration (see Figure 2) with recirculation, the pH adjustment chemical
injection point must be located downstream of the residual sanitizer injection point (if so equipped).
In a Full Flow plumbing configuration (see Figure 3) without recirculation, locate downstream of the pH
adjustment chemical injection point.
Adequate protection from weather, dust and excessive heat.
Like any electronic component, performance and longevity is enhanced by favorable operating conditions. Also,
since each air preparation system and ozone generator is air-cooled, a relatively dust-free, well-ventilated area is
required. No caustic chemicals should be stored in the area surrounding the equipment. A minimum clearance of
six inches from the vents on either side of the ozone generator is required.
The equipment is heavy and requires proper support. Therefore, a clean, dry, level surface should be provided for
the air preparation system and ozone generator. These components should be securely fastened to the surface
using the mounting holes, tabs, and/or mounting bar provided. Make sure suitable wall anchors are used to
support the weight of the system.
The air preparation system and ozone generator are not designed to withstand outdoor elements, including direct
contact with water and/or temperature extremes. Therefore, the equipment must be installed in an environment
consistent with the following operating parameters:
Ambient temperature range: 20°F (-6.5°C) to 95°F (35°C) continuous. If the temperature around the
equipment consistently exceeds 95°F (35°C), additional air-cooling must be provided.
Humidity: 0 90% relative humidity, non-condensing environment
Line voltage: +/-10% of rated input
Note: Equipment installed in extreme environmental conditions will void manufacturer's warranty.
Allow room for the peripheral equipment (booster pump, injector manifold, contact vessel, etc.).
-9-
Installation Procedures – Plumbing
The ozone system should be plumbed using either a sidestream or full flow
configuration. The sidestream loop method takes a portion of the water from the main
flow (see Figure 2) and diverts it into a sidestream downstream of the filter (if so
equipped). Ozone is introduced into the sidestream water and is allowed contact time
with the water before it is returned to the main flow at a point downstream of all other
equipment (heaters, solar panels, etc., if so equipped) in the circulation system. A
booster pump is usually employed to compensate for the flow restriction caused by the sidestream loop and the
injector manifold. If a halogen-type residual sanitizer is utilized, its injection point should be as far downstream as
possible from the point at which the sidestream water returns to the main flow. In a full flow configuration, the
same system components are usually involved and appear in the same order with respect to the direction of flow.
However, all the water in the main flow is allowed contact time with the ozone (see Figure 3). A booster pump
may be necessary to maintain proper flow requirements. If employed, the booster pump is located upstream of the
point at which the ozone injector manifold is installed.
NOTES:
Adequate use of unions and isolation valves is
strongly recommended to facilitate
maintenance and repairs.
Use Schedule 80 PVC for all plumbing
connections wherever possible. Plumbing size
requirements are dictated by the water flow
characteristics of the system.
Make sure to use proper plumbing practices
and secure all plumbing and system equipment
according to local codes.
Ozone is a powerful oxidizer and will degrade
certain materials. Use ozone-compatible
plumbing materials for section(s) of the system
that will come in contact with ozone dissolved
in water. The following is a list of materials that
are compatible with ozone:
PVC Stainless Steel (300 series)
CPVC Viton
Kynar EPDM
Teflon • Concrete
Depending on the application, other
components (psi gauge, flow meter, etc.) may be
installed to assist in monitoring system
parameters.
Step 1: Arrange the ozone system equipment (booster pump, injector and contact vessel) according to mechanical
print or as dictated by equipment layout and serviceability considerations. Do not secure booster pump
and contact vessel to housekeeping pads at this point. Dry fit plumbing as appropriate to insure proper fit
and location before making permanent connections.
Step 2: Install a tee or plumbing saddle into the main water line after the filter (if so equipped) and before the
flow diversion mechanism. The purpose of the mechanism is to restrict water flow so water is diverted
into the sidestream (see Figure 2). If such a mechanism is not present in the system (such as a heater
bypass valve, etc.), it will require installation of a valve (butterfly, gate or ball) or a flow controller.
Step 3: Plumb a line from the tee or plumbing saddle to the booster pump. For serviceability of the equipment in
the sidestream loop, be sure to install an isolation valve between the tee or saddle and the booster pump.
Step 4: Plumb from the booster pump to the injector manifold. Make sure to note the correct direction of flow,
indicated by a blue arrow on the inlet side of the manifold body. The check valve assembly is strapped to
the manifold using wire ties. Remove the assembly; using Teflon® tape, install it onto the top opening of
the injector.
Installation Procedures - Plumbing
-10-
Step 5: Plumb from the injector manifold to the inlet side of the contact vessel. To reduce possible backpressure
to the injector, minimize the number of elbows between the injector manifold and contact vessel. The
contact vessel is a specified size, determined by water flow requirements. ClearWater Tech contact
columns and the 30, 40, 80, and 120-gallon contact tanks have inlet and outlet fittings on the bottom of
the vessel and are designated with arrows showing the direction of flow. Note: The inlet and outlet
arrows on the contact tanks are under the base of the tank. The inlet on the 264, 463 and 850-gallon
tanks is located at the top with the outlet at the bottom.
Step 6: Using a tee or plumbing saddle, plumb from the outlet of the contact vessel back into the main water line.
For serviceability of the equipment in the side stream loop, be sure to install an isolation valve between
the outlet fitting on the contact vessel and before returning to the main water line.
Step 7: Secure the booster pump and contact vessel to solid mounting surfaces using appropriate hardware and
according to local codes. If installing a ClearWater Tech contact column, use a ClearWater Tech contact
column mounting kit and install according to the instructions below. If installing a contact tank, secure to
a solid horizontal surface using mounting flange or feet.
Step 8: Install the contact vessel venting system into the top of the vessel. If using the ClearWater Tech contact
column, the vent kit supplied includes fittings, a control valve and Teflon® tubing. The contact tank
venting system includes an air relief valve, fittings and a length of Teflon® tubing. Depending on
conditions, the vented gas may be directed to an ozone destruct system, to atmosphere or to the low-
pressure side of the water system. Note: Do not direct the tubing to the suction side of any pump in
the system.
Contact Column Installation (If so equipped)
Step 1: Make sure the following hardware items are included in the contact column mounting kit:
'L' bracket • Unistrut bar
• 1/2” concrete anchors • Protective end cap
• 6” clamp assemply • Mounting hardware
Step 2: Referring to Figure 4, mark the two holes for mounting the 'L' bracket to the wall. The bracket should be
located so that the 6” clamp assembly will be approximately 12” from the top of the contact column. Drill
a 1/2” hole at each of the marks, about 3 1/2” deep. Insert a concrete anchor into each hole with the
threaded end facing outward. Slip the 'L' bracket over the threaded ends of the anchors, followed by a
washer for each anchor. Secure the bracket to the wall by threading a nut onto each anchor and tightening.
Step 3: Cut the unistrut bar to the desired length and attach it to the 'L' bracket using hardware provided.
Step 4: Slip the two sides of the 6 clamp into the unistrut bar and then around the contact column. Tighten the
retaining bolt, securing the contact column to the unistrut bar.
Step 5: Slip the protective end cap over the exposed end of the unistrut bar.
Installation Procedures - Plumbing
-11-
Sidestream Plumbing Installation Diagram
Figure 2
Full Flow Plumbing Installation Diagram
Figure 3
Flow Diversion
Mechanism
Filter
Isolation
Valve
Booster
Pump
Ozone Injector
Bypass Valve
Contact
Vessel
Isolation
Valve
Booster
Pump
Isolation
Valve
Service Loop
Isolation
Valve
Isolation
Valve
Ozone Injector
Bypass
Valve
Contact
Vessel
Installation Procedures - Plumbing
-12-
6” Clamp Assembly
with bolt & nut
Unistrut
(cut to length)
Unistrut
Protective
End Cap
Bolts, nuts &
washers (2 ea)
“L” Bracket
Concrete Anchors
with nuts &
washers (2 ea)
Column
Column
Flange
Flange Bolts &
Washers (8 ea)
Diffuser
Riser Tube
Gasket
Flange Nuts &
Washers (8 ea)
Base Flange
Base
Contact Column Installation Diagram
Figure 4
Contact Column Exploded View
Figure 5
-13-
Installation Procedures – Electrical
The CD1500 and CD2000 ozone generators are equipped with universal regulated power
supplies that accept an input voltage from 90-250VAC at 47-63Hz, single phase (1ø).
ClearWater Tech has an assortment of IEC cords for various voltage requirements and outlet
configurations, for use around the world. All possible pre-wiring has been completed at the
factory. Logic schematics have been provided in the Appendix D.
Notes:
All electrical connections should be made by a
licensed, qualified electrician. All local, state
and national codes must be observed.
Make sure all power is off at the main circuit
breaker before making any electrical
connections
Step 1: Conforming to all local, state and national electrical codes, ground the ozone generator to a true earth
ground. Use solid copper bonding wire (usually #8 AWG) from the copper-bonding lug located on the
bottom of the ozone generator to the grounding point.
Step 2: Main Power: Plug the IEC end of the power
cord into the power entry module located at the
bottom of the ozone generator. The other end
can be plugged into any main power source
with input voltage from 90 to 250 VAC at 47 to
63 Hz, single phase. The power consumption of
the unit is shown in the chart on the right.
Step 3: External Loop: The external loop is a true dry contact interface. Note: The termdry contact means
that this loop does not supply output nor accept input voltages. Warning: Supplying voltage to the
external loop will cause damage to the ozone generator and void warranty.
Under normal operation, when this loop has lost continuity the ozone production will stop and the ozone
output will drop to 0%.
Note: When the external loop has lost continuity, main power to the ozone generator will remain
“ON” giving power to the cooling fan(s).
When continuity is present through the external loop the ozone production will continue at whatever
percentage set by the manual ozone output control or the 4-20mA signal.
The external loop, a removable two-position plug with a white 18AWG wire located at the bottom panel
of the ozone generator (see Appendix A), can be interfaced to any control device, i.e., pressure switch,
vacuum switch, flow switch, float switch, ORP controller, PPM controller, or timer. To interface a control
device to the external loop, cut the white 18AWG wire in half. Connect the control device to each leg of
the external loop. If the control device used supplies an output voltage a single pole single throw (SPST)
normally-open relay may be used to create a dry contact interface, see Figure 6 below. Note: Attached to
the white 18 AWG external loop is a warning, THIS CONNECTION IS A DRY CONTACT
ONLY, DO NOT APPLY VOLTAGE”.
Step 4: Manual Ozone Output Control: Turning the control knob counterclockwise will decrease the ozone
output down to 0% while turning the knob clockwise will increase the ozone output up to 100%. The
ozone output level is indicated by the “Ozone Output” LED(s) on the front cover of the ozone generator
(see Appendix, Section A).
Power Consumption
Input Voltage
90-250VAC 47-63Hz
CD1500
1.6-0.8 Amps
CD2000
2.8-1.4 Amps
Installation Procedures - Electrical
-14-
Step 5: Remote 4-20mA Control: A 4-20mA control signal to the ozone generator may be used to control the
ozone generator output. The ozone generator will automatically sense the 4-20mA input signal and
override the setting of the manual ozone output control. Based on the 4-20mA signal, ozone output will
increase or decrease: 4mA = 0% ozone output, 20mA = 100% ozone output. The ozone output level is
indicated by the “Ozone Output” LED(s) on the front cover of the ozone generator (see Appendix,
Section A). Note: If the remote 4-20mA signal fails or is missing, the system will default to the
manual ozone output setting. Check and adjust the manual ozone output control knob to avoid
over-ozonation.
Remote 4-20mA Control Setup:
Step 1: Mount the 4-20mA controller to a suitable vertical surface according to the installation manual
supplied with the controller.
Step 2: Wire the #22 AWG orange ‘positive’ (+) lead from the ozone generator to the 4-20mA controller
according to the manual supplied with the controller.
Step 3: Wire the #22 AWG purple ‘negative’ (-) lead from the ozone generator to the 4-20mA controller
according to the manual supplied with the controller.
Step 4: Complete the required programming and calibration steps as outlined in the installation manual
supplied with the 4-20mA controller.
Step 6: Air Preparation System Power: 120VAC systems only: plug the power cord into main power. 240VAC
systems only: the power cord must be hard wired to the main power source (Black-L1, White-L2/N and
Green-Ground). Notes: Be careful to not exceed the rated flow of the air preparation system. Doing
so will over draw the system and could lead to premature failure. Vacuum from the venturi must be
interrupted if the air prep system is not “ON; failure to do so will damage the air prep system.
External Loop Electrical Interface
Figure 6
120 VAC Signal
L1
N
Power from
OPR, PPM,
pump or timer
120V
Coil
Interface
Relay
External
Loop
240/220 VAC Signal
L1
N/L2
Power from
OPR, PPM,
pump or
timer
240V
Coil
Interface
Relay
External
Loop
-15-
Booster Pump
Ozone Injector
Water Flow
Ozone Generator
Vacuum
Break
Air Prep In
Ozone Out
Air Prep
System
Installation Procedures – Pneumatic
This section outlines the steps required to complete the ozone system pneumatic hook-ups. The system
components include the air preparation system, ozone generator, vacuum break, and ozone injector manifold (see
Figure 7). The air preparation system provides the ozone generator with a source of dry, oil-free oxygen-enriched
air (90% +/- 3% oxygen purity at -60˚F dew point). The air is drawn from the ozone generator (where ozone is
produced from the oxygen in the air stream) and through the vacuum break by the suction created at the ozone
injector manifold.
Typical Pneumatic Hookup
Figure 7
Hook-Up: Air preparation system-to-ozone generator
Step 1: Setup the air preparation following the instructions provided with the air preparation system. Make sure
the air preparation system you select can deliver that amount of air flow required without over drawing
the sieve beds. Warning: Make sure to read and follow the operating instructions of the air
preparation system as damage could occur to the air preparation system if the flow rate is too high.
Step 2: Teflon® tape and attach brass barb provided to the PSA oxygen concentrator outlet (if so required). A
typical oxygen concentrator system is shown below in Figure 8 as a reference.
Step 3: Using a suitable length of 3/8” braided tubing provided, attach one end of the tubing to the oxygen
concentrator system to one end of the indicator cartridge. Secure the tubing to the brass fittings with the
hose clamps provided.
Step 4: Using a suitable length of 3/8 braided tubing, attach tubing to the barb located on the oxygen
concentrator, then attach the other end of the tubing to the brass barb located at the bottom of the ozone
generator. Secure the tubing to the fittings with the hose clamps provided.
Installation Procedures - Pneumatic
-16-
Compressor Inlet Filter
Sieve Bed
Hour Meter
SCFH Air Flow Meter
Oxygen Outlet
Main Power Cord
Compressor
Typical Oxygen Concentrator Detail
Figure 8
Hook-Ups: Ozone generator-to-vacuum break & vacuum break-to-injector manifold
The ClearWater Tech vacuum break provides a positive atmosphericbreakbetween the ozone injector manifold
and the ozone generator, preventing water from flowing back into the ozone generator should the venturi check
valve fail. Under normal operating conditions, the vacuum break's flapper valve (see Figure 9) is closed, allowing
the vacuum created by the venturi to draw the output gas from the ozone generator. If the check valve at the
venturi begins to leak or fails completely, vacuum is interrupted and water will flow toward the ozone generator.
With the vacuum break properly installed between the venturi and the ozone generator, the water will flow down
the riser tube (away from the ozone generator) and out to drain, protecting the ozone generator from potential
water damage.
Step 1: Select a suitable vertical surface that is accessible and in close proximity to both the ozone generator and
the ozone injector manifold.
Step 2: Install the two Clic® mounting clamps provided onto the vertical surface so that the vacuum break is in a
vertical position and the drain holes are below the level of the ozone generators ozone outlet fitting. One
clamp should be located so it fits around the Riser Tube Elbow, and the other so it fits around the bottom
of the Lower Tee (see Figure 9).
Step 3: Remove the Fill Port Cap located on top of the Riser Tube and fill the Riser Tube with clean water (no
particulate matter) until "Fill Level" line indicated in Figure 9.
Step 4: Re-install the Fill Port Cap, using pliers or a wrench to tighten. Note: Do not over tighten as damage to
PVC fittings may occur.
Step 6: Connect one end of a suitable length of Teflon® ozone delivery line to the ozone generator’s ozone outlet
fitting (see Appendix, Section A). Attach the other end of the Teflon® delivery line to the fitting
threaded into the Upper Tee. As an additional backflow prevention measure, loop this length of tubing as
high as is practical between the two connection points.
Step 7: Connect one end of a second length of Teflon® delivery line to the fitting threaded into the Lower Tee.
The other end of the delivery line will be attached to the fitting located on top of the check valve
assembly.
Step 8: Adjustments to the valve on the ozone injector manifold will be necessary. These steps are covered in the
Start-up and Calibration Procedures.
Installation Procedures - Pneumatic
-17-
Vacuum Break Detail
Figure 9
Ozone Flow
Ozone Flow
Riser Tube
Drain Barb
Overflow Tube
Fill Level
Flapper Check Valve
Ozone
Outlet
Check Valve Assembly
Ozone Injection Manifold
Ozone Generator
Fill Port Cap
Upper Tee
Low Tee
Mounting Clamps
Riser Elbow
-18-
Start-Up and Calibration
The previous sections of this manual have involved comparatively static procedures making electrical and
pneumatic connections, fitting pipe, etc. This section involves the dynamic process of starting up and balancing
the components of the ozone system, including initiating water flow, making air and water flow adjustments, etc.
Maximum performance and reliability is achieved when the prescribed air flow is maintained at the ozone
generator. Air from the air preparation system is flowing through the ozone generator under a slight vacuum
(created by the ozone injector manifold).
Air Preparation System, Ozone Generator & Ozone Injector
Warning: Disconnect the External Loop dry contact from the ozone generator while performing all start-up
procedures. Failure to do so may result in ozone escaping to atmosphere.
Step 1: Make sure all isolation valves in the ozone water system are open (Figures 2 or 3 show recommended
isolation valve locations).
Step 2: Start-up hydraulics. Allow the water system to reach hydraulic equilibrium (contact vessel full, off-gas
vent operating, etc.) and observe for plumbing leaks. Note: Water flow must be established through
the main water pump and the ozone system booster pump (if so equipped).
Step 3: Close the ball valve on the injector manifold about half way.
Step 4: Using your thumb, check for the presence of vacuum (suction) at
the ozone injection manifold check valve assembly or use a
ClearWater Tech vacuum test assembly to check vacuum at the
injector port. If no suction is present, continue to close the ball
valve on the injector manifold until vacuum is detected. If using the
vacuum test assembly, check the VAC/PSI gauge for vacuum. If
the needle is in the red zone on the pressure (PSI) side of the gauge,
gradually close the ball valve on the injector manifold until the
needle moves into the green zone. If the needle is in the red zone
on the vacuum (in.Hg) side of the gauge, gradually open the ball valve on the injector manifold until the
needle moves into the green zone. While vacuum is in the green zone you must be able to achieve proper
SCFH (Standard Cubic Feet per Hour) of air flow (see the Pneumatic Operating Parameters” chart for
venturi SCFH required, Figure 10).
Step 5: Make sure electrical power is on to all ozone system electrical components. The main power switch of
the air preparation system must be in the “ON” position (if so equipped, see Figure 8). Setup the air
preparation following the instructions provided with the air preparation system. Make sure the air
preparation system you select can deliver that amount of air flow required without over drawing the
sieve beds. Warning: Make sure to read and follow the operating instructions of the air
preparation system as damage could occur to the air preparation system if the flow rate is too
high.
Step 6: Connect the Teflon® ozone delivery line from the vacuum break to the ozone inlet fitting located at the
ozone injection manifold check valve assembly.
Start-Up and Calibration
-19-
Step 7: Observe the air flow through the system using the flow meter on the front of the air preparation system
(See Figure 8). Using the needle valve on that flow meter make sure the flow is in a range that will not
over draw the sieve beds. Warning: Make sure to read and follow the operating instructions of the
air preparation system as damage could occur to the air preparation system if the flow rate is too
high.
Step 8: Perform a final check of all air connections from the air preparation system to the ozone injector
manifold. Repair leaks as required. Check all system water connections, including the ozone injector
manifold, vacuum break and contact vessel. Repair leaks as required. Note: The check valve at the
ozone injector manifold may make a humming noise. This is normal.
Step 10: Reconnect the External Loop connector to the ozone generator.
Step 11: See “Installation Procedures Electrical” for instruction on how to adjust ozone output.
Ozone System Power Up
When the ozone system is powered up with the external loop connected to the ozone generator, the manual ozone
control allowing ozone production, the unit will begin generating ozone. The drive boards Self-Resonating
Technology (SRT) will begin by characterizing the drive system at the temperature, pressures, and flows the
reaction chamber is currently experiencing. You will hear and audible sweep of the drive frequency from high to
low as the drive board maps the resonant point of the system. For best results bring the pressure and flow through
the system up to normal operation before powering up the ozone generator.
Vacuum Break
Check the water level in the vacuum break, making sure it is above the flapper valve (see Figure 9). If water is not
pressing downward on the flapper valve it will open, causing a loss of vacuum. A loss of vacuum means ozone
cannot flow from the vacuum break, which in turn can cause an ozone leak. Note: If the vacuum break must be
refilled with water disconnect the External Loop from the ozone generator and disconnect the Teflo
ozone delivery line from the ozone inlet fitting of the vacuum break. Once the vacuum break is filled,
reconnect the ozone delivery line first, then reconnect the External Loop.
Ozone Destruct System
Adjust the small ball valve at the tee of the water trap (see Figure 1) so that only a small amount of water is
“spitting” into the trap. This will indicate that the contact vessel is full and only a very small amount of water is
allowed to escape.
Start-Up and Calibration
-20-
Pneumatic Operating Parameters
Figure 10
CD1500
Operating Range
Optimum
Air prep system air flow
Ozone generator total air flow (Air prep gauge)
Injector manifold air flow
Injector manifold injector
5 to 6 scfh
6 to 7.2 cfh
5 to 6 scfh
-3 to -8 in. hg.
6 scfh
7.2 cfh
6 scfh
-5 inches
CD2000
Operating Range
Optimum
Air prep system air flow
Ozone generator total air flow (Air prep gauge)
Injector manifold air flow
Injector manifold injector
10 to 12 scfh
12 to 14.4 cfh
10 to 12 scfh
-3 to -8 in. hg.
12 scfh
14.4 cfh
12 scfh
-5 inches
-21-
Maintenance
Maintenance of the ozone system is critical to its longevity and operating efficiency. While all
system components are built to provide years of reliable service with minimum maintenance,
following the procedures outlined below is strongly recommended.
All maintenance procedures have been segmented by interval: daily, monthly, semi-annual
and annual. Daily procedures involve quick, visual checks for changes in normal operating
conditions. Monthly, semi-annual and annual procedures include cleaning and/or replacement of certain critical
parts.
NOTES:
The ozone generator warranty states that it
“does not extend to any product or part
which has been damaged or rendered
defective as a result of use of parts not sold by
ClearWater Tech, or service or unit
modification not authorized by ClearWater
Tech” Please contact your ClearWater Tech
dealer if you have any questions about any
maintenance procedure before you begin that
procedure.
CAUTION: Observe all common safety
practices and review the “Safety Warnings and
Instructions” section before attempting any
maintenance procedure that requires the use of
tools and/or shutting down the ozone system.
Daily Procedures
Air Preparation System
Power Switch: Check the power switch on the air preparation system (see Figure 8), if so equipped.
Indicator Cartridge: Inspect the air preparation system indicator cartridge. A change in the blue crystals to a
light pink or white color indicates the presence of moisture in the feed gas coming from the air preparation
system. If such a change is observed, refer to the Troubleshooting Guide.
Air Flow: Check the air flow gauge on the air preparation system (see Figure 8). Make sure the air flow is
within the acceptable SCFH range for the unit. See the Pneumatic Operating Parameters in Figure 10.
Warning: Make sure to read and follow the operating instructions of the air preparation system as
damage could occur to the air preparation system if the flow rate is too high.
Ozone Generator
Check the ozone level to make sure it remains at the correct set point
Air Flow: Check the air flow gauge located on the front control panel. Compare the CFH flow on the flow
gauge to the Pneumatic Operating Parameter in Figure 10 to insure the proper output is being achieved.
Warning: Make sure to read and follow the operating instructions of the air preparation system as
damage could occur to the air preparation system if the flow rate is too high
Vacuum: Check the vacuum level in the system. Adjust if necessary by following steps outlined in the “Start-
Up & Calibration” section.
Vacuum Break
Water Level: Check the water level in the vacuum break. Make sure it is above the flapper valve in the
overflow tube. Fill as required by removing the threaded fitting on top of the riser tube until water is up to the
‘Fill Level’ in the overflow tube (see Figure 9).
Maintenance
-22-
Injection Manifold
Check Valve: Inspect the Teflon® ozone delivery line that runs between the vacuum break and the check
valve assembly on the suction port of the ozone injector manifold. If water is observed in the delivery line
near the check valve assembly, the check valve has failed. See Troubleshooting Guide.
Monthly Procedures
Air Preparation System
Cooling Fan Operation: Check to make sure the cooling fan mounted on the side panel of the air preparation
system is operating (if so equipped). If not, refer to the Troubleshooting Guide.
Cover Filter: Check the cover filter element mounted on the side of the air preparation system and clean as
required. Operating conditions in the equipment area will dictate the frequency required for this procedure.
Remove the filter element and clean with soap and water, drying them completely before re-installing.
Ozone Generator
Drive Module Operation: The Drive Module is made up of two components: the drive board and the drive
transformer. Check for illumination of the drive module "Ozone Output" LED(s) (for LED locations, see
Figure 11); if not illuminated see Troubleshooting Guide. This procedure is to observe the complete operating
function of the drive module(s). Remove the cover and override the safety switch. CAUTION: Do not touch
anything inside the ozone generator while the system is energized and the cover removed! Please consult
your ClearWater Tech dealer before attempting this procedure.
Main Power LED: When illuminated, this “Green” LED indicates that main power is supplied to the drive
module up to the “on board” fuse of the drive board.
Transformer Power LED: When illuminated, this “Green LED indicates that 48V Buss power is
available to the drive module transformer (XFMR) from the “on board fuse of the to the drive
transformer.
Ozone Output LED: The Amber” ozone output LED will illuminate when ozone drive is being
generated. The LED will also pulse as the output increases or decreases with either the Manual Ozone
Output Control located on the bottom of the ozone generator (see Appendix A), or from a Remote 4-
20mA signal (see “Installation Procedures Electrical”).
Fault LED: When illuminated, this “Red” LED indicates that there is a fault with the drive module or the
Ozone Reaction Chamber. If this LED is illuminated, refer to the Troubleshooting Guide. Notes: If the
drive module goes to a fault condition, the drive board will restart every 15 seconds. If the fault is
not remedied the drive module will continue to go into a fault mode. When the drive module is in
fault mode ozone will not be generated.
Before proceeding further replace the ozone generator cover.
Cooling Fan Operation: Check to make sure the two cooling fans (mounted on the bottom panel of the ozone
generator cabinet) are operating. If not, refer to the Troubleshooting Guide.
Cooling Fan Filters: Check the cooling fan filter elements mounted on the bottom of the ozone generator (see
Appendix A) and clean as required. Operating conditions in the equipment area will dictate the frequency
required for this procedure. Remove the filter element and clean with soap and water, drying them completely
before re-installing (see Figure 12).
Booster Pump(s)
Strainer Baskets: Check and clean the strainer basket in the booster pump(s) as required (if so equipped)
Maintenance
-23-
CD1500 and CD2000 High Output Drive Module
Figure 11
Ozone Generator Cooling Fan Assembly
Figure 12
Drive Board
Transformer Output Connector
Ozone Output LED
In/Out Signal Header
Fuse
Transformer – XFMR LED
Drive Board Main Power LED
Fault LED
24VDC Output Connector
Variable Input Connector
DC Power Input Connector
Fan
Ozone Generator Bottom Panel
Finger Guard
Fan Filter Element
Fan Filter Grill
Maintenance
-24-
System Shutdown Procedures
CAUTION: The ozone generator operates at high voltage. Follow these steps carefully before performing
any semi-annual or annual maintenance procedures.
Step 1: Turn off power to any peripheral system hydraulic components and air prep system.
Step 2: Turn the Main Power switch on the ozone generator to the “OFF position.
Step 3: Disconnect the power to the ozone system either at the service disconnect box (if so equipped) or main
circuit breaker.
Semi-Annual Procedures
CAUTION: Follow system shutdown procedures (outlined above) before performing any of the following
steps.
Air Preparation System
Air Inlet Filter: Replace the air compressor inlet filter on the air preparation system module (see Figure 8).
Note: Manufacturers' recommended replacement interval is 4,000 hours of operation. Operating
conditions in the equipment area will dictate the required frequency of this procedure.
Annual Procedures
CAUTION: Follow system shutdown procedures before performing any of the following steps.
Air Preparation System
Compressors: Following the procedures outlined in the compressor rebuild kit, rebuild the two compressor
heads on each air preparation system module (see Figure 8). Note: Manufacturers' recommended interval
is 5,000 to 12,000 hours of operation. Compressor performance and/or operating conditions in the
equipment area will dictate the required frequency of this procedure.
Ozone Generators
Cooling Fan Filters: Clean or replace the cooling fan filter elements as required.
Inline Filter: Replace the inline particulate filter.
Reaction Chambers: Remove and disassemble the reaction chamber(s) according to the steps outlined below
(see Figure 13). Check the chamber interior and dielectric tube for oil, dirt or moisture.
Reaction Chamber Removal and Disassembly
Note: Disassembly and service of the reaction chamber is a technical, delicate and critical procedure.
Please consult your ClearWater Tech dealer before attempting this procedure.
Step 1: Make sure all power to the ozone generator has been disconnected according to the System Shutdown
Procedures” outlined above.
Step 2: Unplug the electrical connections from the drive module.
Step 3: Disconnect tubing connections from the fittings on both ends of the reaction chamber
Step 4: Remove the 4 nuts holding the reaction chamber to the chassis.
Step 5: Remove the reaction chamber from the ozone generator.
Step 6: Disconnect the high voltage lead from the drive module.
Step 7: Remove retaining screws from the two end caps (4 each).
Step 8: Using a gentle back-and-forth twisting motion, remove the non-high voltage end cap (the one without
the white power lead attached) from the heat sink/cathode assembly.
Maintenance
-25-
Step 9: Remove the high voltage end cap and dielectric from the heat sink/cathode assembly.
Step 10: With contact brush attached, remove the brush adapter nut from the high voltage end cap.
Step 11: Inspect the dielectric, end caps and cathode for breakage, corrosion or debris. Clean and/or replace parts
as necessary. If cleaning and/or parts replacement is not required, re-assemble the reaction chamber per
the instructions below.
Assembly and Re-installation
Step 1: Make sure the glass dielectric is clean (free of dust, dirt, grease, oils, etc.).
Step 2: Prepare the end caps for re-assembly by replacing the O-rings. Thread the hex brush adapter nut, with
contact brush attached, onto the end of the high voltage end cap (cap with the white power lead attached)
center screw.
Step 3: Using a gentle twisting motion, press the non-high voltage end cap onto the heat sink/cathode assembly
until flush with the heat sink cooling fins. Note: See Figure 13 for correct orientation of end cap.
Step 4: Slide the four end cap retaining screws through the holes in the non-high voltage end cap, aligning them
with the heat sink screw bosses. Thread screws into screw bosses until heads are snug against the end
cap.
Step 5: Roll the high voltage anode (foil-like material) lengthwise, preserving the longer dimension. Insert the
rolled anode into the dielectric. Center the anode in the dielectric (approximately 1/2” from either end of
the glass), making sure it is rolled squarely.
Step 6: Slide the dielectric into the heat sink/cathode assembly. Seat the dielectric into the O-rings of the non-
high voltage end cap by applying pressure with a gentle twisting motion. (There must not be any dirt,
debris, oils or fingerprints on the dielectric upon re-installation).
Step 7: Slowly insert the high voltage end cap assembly into the dielectric. Note: Do not bend center wire of
the brush during this procedure. It is normal for the bristles to bend. Using a gentle twisting motion,
press the high voltage end cap onto the heat sink/cathode assembly until flush with the heat sink cooling
fins.
Step 8: Slide the four end cap retaining screws through the holes in the end cap, aligning them with the heat sink
screw bosses. Thread screws into screw bosses until heads are snug against the end cap.
Step 9: Re-install complete reaction chamber assembly into the ozone generator by following the Removal and
Disassemblyinstructions in reverse order, from Step 6 to Step 2. Follow steps outlined in the “Start-Up
and Calibration” section to re-start the ozone system.
Maintenance
-26-
2” Reaction Chamber – Exploded View
Figure 13
Vacuum Break
Cleaning: Disconnect ozone delivery lines. Remove the vacuum break from mounting clamps. Disconnect the
overflow tube from flapper valve, open flapper and clean the seat with a soft cloth. Remove riser tube
threaded fitting and flush riser tube with water. Re-assemble and re-install vacuum break, making sure to add
water to correct level (see Figure 9).
Injector Manifold
Check Valve: Replace the check valve located at the ozone injection manifold. Note: Because the system is
in the shutdown mode, no vacuum is present at the injector. Therefore, it is normal for some water to
be flowing from the injector during this procedure.
Contact Vessel
Cleaning: Contact Column only. Inspect the diffuser slots at the top of the contact column riser tube. If they
are clear, no further maintenance is required. If the slots are fouled, disassemble the column and clean as
required, following the steps outlined below (see Figure 5).
Step 1: Make sure the isolation valves before and after the contact column are closed.
Step 2: Disconnect the vent line from the top of the contact column.
Step 3: Remove the bolts in the 6” base flange.
Step 4: Remove the column, lifting it over the interior riser tube.
Step 5: Remove and clean the diffuser.
Step 6: Inspect the flange gasket and replace if necessary.
Step 7: Reassemble the contact column and attach vent lines.
High Voltage End Cap
High Voltage
Lead
Contact Brush
Brush Adapter Nut
Oxygen Inlet Fitting
High Voltage Anode
Glass Dielectric
End Cap Retaining
Screw and Washer
Heat Sink and Cathode
Bottom End Cap
Ozone Outlet Fitting
27
Troubleshooting
Air Preparation
Problem/Symptom
Possible Cause
Solution
Unit not operating
No power to system
Power switch in “OFF” position
Incorrect wiring
Check main power to system
Turn switch to “ON” position
See “Installation Procedures
Electrical”
Low air flow or no air flow
Flow meter out of adjustment
Fouled compressor inlet filter
Compressor not functioning
Adjust flow meter, see “Start-Up
and Calibration Step 5
Replace inlet filter
Rebuild or replace as required
Compressor pressure relief valve
making noise
Pressure relief valve not operating
Excessive back pressure in system
Pinched tubing
Compressor not functioning
ATF not operating
Replace pressure relief valve
Check the check valve for proper
operation, replace as required
Replace tubing
Rebuild or replace as required
Repair or replace ATF as required
Unit is making excessive noises
Unit not properly secured to floor
Shipping damage
Fan Blocked
Packaging material not removed
Place unit on a flat level surface
Locate damage and repair/replace
parts
Clear obstructions
Remove packaging material
Ozone Generator
Problem/Symptom
Possible Cause
Solution
System is not ON”
No power to unit
Power switch in “OFF” position
Blown Fuse
Incorrect wiring
Check main power to system
Turn switch to “ON” position
Replace fuse
See “Installation Procedures
Electrical”
Circuit breaker trips
Incorrect wiring
Circuit breaker amperage does not
match draw
Unit flooded with water
See “Installation Procedures
Electrical”
Replace with correct circuit breaker
Asses damage, correct cause and
rebuild as required
Receive an electric shock upon
touching the unit
Incorrect wiring
Unit not grounded
Unit flooded with water
See “Installation Procedures
Electrical”
Ground unit according to local codes
Asses damage, correct cause and
rebuild as required
Drive Board 12V Green Power LED
does not illuminate.
No power to drive module from
power supply
Loose wires or connectors
Blown drive module “on board” fuse
Check main power to unit
Test voltage from power supply to
drive module (see “Appendix E
Drive Module Input Voltages”)
Check for loose wires or connectors
Replace “on board” fuse
Troubleshooting
28
Ozone Generator - Continued
Problem/Symptom
Possible Cause
Solution
Drive Board XFRM Green Power LED
does not illuminate
No power to the drive module from
power supply
Loose wires or connectors
Blown drive module “on board” fuse
Check main power to unit
Test voltage from power supply to
drive module (see “Appendix E
Drive Module Input Voltages”)
Check for loose wires or connectors
Replace “on board” fuse
Drive Board Ozone LED does not
illuminate
Unit is under the control of a remote
4-20mA current signal
Manual Ozone Output is turned
down to 0%
Loose wires or connectors
Drive board in “Fault” mode
Check the remote signal
Disconnect the remote signal
Turn up the manual ozone output
control by pressing the right hand
button. See “Ozone Generator
Program Setup Output Screen
See Troubleshooting, “Drive Board
Power Problem” above
See Troubleshooting, “System
Fault” below
A 4-20mA control signal is being used
but does not appear to adjust the ozone
output.
The 4-20mA signal is not being
sensed correctly
Check for loose wires or
connections
See “Installation Procedures
Electrical”
Drive Board in Fault, Single Flash
The drive board can not get enough
power into the reaction chamber.
Loose wire harness connection from
the drive board to the drive
transformer
Drive board incorrectly characterized
the system on startup
Loose or disconnected High Voltage
Lead to transformer
Excessive dirt or debris in ozone
reaction chamber
Water in ozone reaction chamber
Broken dielectric
Failed drive board
Failed drive transformer
Check all wires and connectors
With pressure and flow at normal
operating conditions, restart the
ozone generator.
Attach High Voltage Lead to
transformer
Clean the dielectric and replace O-
rings
Clean the dielectric and replace O-
rings
Replace dielectric
Replace drive board
Replace drive transformer
Drive Board in Fault, Double Flash
The drive board’s feedback had a series
of sudden dips indicative of unusual
arcing occurring somewhere in the
system.
Loose wire harness connection from
the drive board to the drive
transformer
Loose or disconnected High Voltage
Lead to transformer
Excessive dirt or debris in ozone
reaction chamber
Water in ozone reaction chamber
Broken dielectric
Failed drive board
Failed drive transformer
Check all wires and connectors
Attach High Voltage Lead to
transformer
Clean the dielectric and replace O-
rings
Clean the dielectric and replace O-
rings
Replace dielectric
Replace drive board
Replace drive transformer
Troubleshooting
29
Ozone Generator - Continued
Problem/Symptom
Possible Cause
Solution
Drive Board in Fault, Triple Flash
The thermal switch on the board has
closed indicating that it was exposed to
temperatures exceeding 140F.
Unit is overheating
Check fan for proper operation and
clean fan filter
Check operating temperature
See “Installation Procedures
Getting Started, Equipment
Placement”
Fan not operating
Fan obstructed
Power supplies not operating
Fan inoperable
Remove obstruction
Check main power, check fuses,
repair and replace as required
Replace fan
Low air flow or no air flow
Air preparation system not operating
properly
Air preparation system being
powered from ozone unit
Fouled inline filter
Air leak
Incorrect wiring to air prep system
See “Start Up and Calibration Step
5”
See “Ozone Generator Program
Setup Setup Screen 5”
Change inline filter
Check all fittings, tighten as needed
See “Installation Procedures
Electrical”
Unit flooded with water
Defective check valve
Vacuum break incorrectly setup
Defective vacuum break
Replace check valve(s)
See “Installation Procedures
Pneumatic, Hook-Ups”
Replace vacuum break
Assess damage, repair as required
Ozone smell detected in or around
ozone generator
Insufficient vacuum at venturi
Loose internal fittings
Defective O-ring seals in reaction
chamber(s)
Defective dielectrics
Adjust injector see “Start-Up and
Calibration Steps 1-4”
Check all fittings, tighten as needed
Check and replace as required
Check and replace as required
Ozone Injection/Contacting
Problem/Symptom
Possible Cause
Solution
Water backflow past injector check
valve
Defective check valve
Replace check valve
Water bubbling in vacuum break
No vacuum
Debris on seat of vacuum break
flapper valve
See “Start-Up and Calibration”
Clean seat of flapper. See
“Maintenance Procedures Annual”
Low Vacuum
Hydraulics/Pneumatics out of
adjustment
Defective check valve
Hydraulic back pressure
Defective solenoid valve
No water in vacuum break
Booster pump not functioning
properly
See “Start-Up and Calibration
Steps 1-4”
Replace check valve
Back wash filter (if so equipped)
Check for obstruction in venturi
Rebuild or replace as required
Fill vacuum break with water. See
“Start-Up and Calibration Vacuum
Break
Check booster pump (contact
dealer)
Troubleshooting
30
Ozone Injection/Contacting – Continued
Problem/Symptom
Possible Cause
Solution
High Vacuum
Hydraulics/Pneumatics out of
adjustment
Change in hydraulics excessive
water flow through ozone injector
See “Start-Up and Calibration
Steps 1-4”
See “Start-Up and Calibration
Steps 1-4”
Ozone smell detected in or around
vacuum break or ozone injector
No vacuum
Loose fittings
Broken fittings
Adjust injector see “Start-Up and
Calibration Steps 1-4”
Check all fittings, tighten as needed
Check and replace as required
31
Shown: ClearWater Tech OXS90 Air
Preparation System with out Cover
Appendix A – Specifications
Air Preparation System (Aerous 15 Shown)
Air Prep System
Specifications
Oxygen Output/SCFH
Aerous 8
19.75” H x 11.89W x 13.75D
68 lbs (with cover)
90% (+/-3%) @ 8 scfh, 10 PSI
Aerous 15
20.50H x 12.64W x 15.10D
75 lbs (with cover)
90% (+/-3%) @ 15 scfh, 10 PSI
Compressor Inlet Filter
Hour Meter
Power Indicator Light
SCFH Air Flow Meter and
Adjustment Valve
Main Power Cord
Oxygen Outlet
Sieve Beds
Solenoid Valves
Compressor
Control Board
Appendix A - Specifications
32
CD1500 – Ozone Generator
Shown: ClearWater Tech CD1500 Ozone Generator
OZONE GENERATOR
SPECIFICATIONS
OZONE OUTPUT/SCFH
CD1500
27” h x 9.25” w x 5.5” d, 32 lbs
10g/h, 3%
@ 7scfh PSA Oxygen
Mounting Hole Measurement
17.75” h x 10.50” w
Ozone Output LED
Drive Board and Drive
Transformer (Under Boards)
Power Supplies
Reaction Chambers
4-20mA Control Board
Inline Particulate Filter
Cover Safety Switch
External Loop
Fan and Fan Filter
Remote 4-20mA Connector
Manual Ozone Output Adjustment Knob
External Loop Connector
Air Prep Inlet
Ozone Output
Main Power Light
Power Entry Module – OFF/ON Switch,
Cord Input, Fuse Carrier
Bonding/Ground Lug
Appendix A - Specifications
33
CD2000 – Ozone Generator
Shown: ClearWater Tech CD2000 Ozone Generator
OZONE GENERATOR
SPECIFICATIONS
OZONE OUTPUT/SCFH
CD2000
23.7” h x 20.25” w x 5.5” d, 49 lbs
20g/h, 4%
@ 14scfh PSA Oxygen
Mounting Hole Measurement
13.5” h x 21.75w
Ozone Output LEDs
Fan and Fan Filter
Ozone Output
Air Prep Inlet
Fan and Fan Filter
Main Power Light
Manual Ozone Output Adjustment Knob
External Loop Connector
Remote 4-20mA Connector
Power Entry Module – OFF/ON Switch,
Cord Input, Fuse Carrier
Bonding/Ground Lug
Drive Board and Drive Transformers (Under
Boards)
Reaction Chambers
Power Supplies
Inline Particulate Filter
4-20mA Control Board
Cover Safety Switch
External Loop
34
Appendix B – Parts List
Air Preparation System
Ozone Generator – CD1500 and CD2000
Description
Part Number
Reaction Chamber Complete
RCC7
Dielectric Anode 2”
RCC71
Non High Voltage End Cap
RCC107
High Voltage End Cap
RCC102
O-ring Set
ORS30
Drive Module Transformer
HVT275
Drive Module Board
CCA1231
Power Supply CD2000
PSR822
Power Supply CD1500
PSR820
Cooling Fan 24VDC
FA46
Cooling Fan Filter
FA40
Inline Particulate Filter
FLT34
Fuse, Bussmann 5 amp, 250VAC Slow Blow, Main Power
FUS20
Fuse, Littelfuse Minifuse 297005 5 amp, 32VAC, Drive Board
FUS75
Description
AEROUS 8
Part Number
AEROUS 15
Part Number
Control PCB 120 VAC 60Hz
OXU372
OXU377
Control PCB 220/240 VAC 50/60Hz
OXU386
OXU378
Solenoid Valve Assembly
OXU379
OXU379
Compressor 120VAC 60Hz
OXU373
OXU340
Compressor 220/240 VAC 50/60Hz
OXU374
OXU345
Encloser Filter
OXU350
OXU351
Inlet Filter Package
OXU371
OXU371
Maintenance Kit
ASP70A
ASP75A
Rebuild Kit
ASP71A
ASP76A
35
Appendix C Maintenance Kit
Air Preparation System
ASP70A – Maintenance Kit – AEROUS 8
Part Number
Quantity
Description
OXS371
1
Oxygen Concentrator Replacement Compressor Inlet Filter
OXS350
1
Oxygen Concentrator Replacement Enclosure Filter
ASP71A – Rebuild Kit AEROUS 8
Part Number
Quantity
Description
OXS379
1
Oxygen Concentrator Solenoid Valve Assembly
OXS375
2
Oxygen Concentrator Sieve Bed
ASP75A – Maintenance Kit – AEROUS 15
Part Number
Quantity
Description
OXS371
1
Oxygen Concentrator Replacement Compressor Inlet Filter
OXS351
2
Oxygen Concentrator Replacement Enclosure Filter
ASP71A – Rebuild Kit – AEROUS 15
Part Number
Quantity
Description
OXS379
1
Oxygen Concentrator Solenoid Valve Assembly
OXS381
2
Oxygen Concentrator Sieve Bed
Ozone Generator
ASP125C – Maintenance Kit – CD1500 Ozone Generator
Part Number
Quantity
Description
CKV21
1
Check Valve
FA40
1
4in Fan
FLT34
1
Filter Inline particulate filter
FUS20
5
Fuse Bussmann 5 amp, 250VAC Slow Blow, Main Power
ORG10
2
O-ring 2 CD reaction chamber, small
ORG110
4
O-ring 2 CD reaction chamber, large
ASP128F – Maintenance Kit – CD2000 Ozone Generator
Part Number
Quantity
Description
CKV22
1
Check Valve
FA40
2
4in Fan
FLT34
1
Filter Inline particulate filter
FUS20
5
Fuse Bussmann 5 amp, 250VAC Slow Blow, Main Power
ORG10
4
O-ring 2 CD reaction chamber, small
ORG110
8
O-ring 2 CD reaction chamber, large
36
Appendix DLogic Schematics
CD1500
Appendix D – Logic Schematics
37
CD2000
38
Appendix E – Drive Module Input Voltages
24VDC
24VDC
48VDC
- G +
39
Appendix F – Warranty Information
ClearWater Tech, LLC. Limited One-Year Warranty
Summary of the Warranty
ClearWater Tech, LLC (“CWT”) makes every effort to assure that its products meet high quality and durability standards and warrants
the products it manufactures against defects in materials and workmanship for a period of one (1) year, commencing on the date of
original shipment from CWT, with the following exceptions: 1) The warranty period shall begin on the installation date if the
installation is performed within 90 days of the original shipment from CWT; 2) The warranty period shall begin on the date of the bill
of sale to the end user if the installation date is more 90 days after the original shipment date. To validate the warranty, a warranty
card, accompanied by a copy of the bill of sale, must be returned to CWT and must include the following information:
End user name
Complete address, including telephone number
Date installed
Complete model and serial number information
Name of company from which the unit was purchased
Repairs and replacement parts provided under this warranty shall carry only the unexpired portion of this warranty or 90 days,
whichever is longer.
Items Excluded from the Warranty
This warranty does not extend to any product and/or part from which the factory assigned serial number has been removed or which
has been damaged or rendered defective as a result of:
An accident, misuse, alteration or abuse
An act of God such as flood, earthquake, hurricane,
lightning or other disaster resulting only from the forces of
nature
Normal wear and tear
Operation outside the usage parameters stated in the
product user’s manual
Use of parts not sold by CWT
Service or unit modification not authorized by CWT
Check valve/solenoid valve failure
Damage which may occur during shipping
Failure to meet service requirements as outlined in the I &
O manual
Obtaining Service Under the Warranty
Any product and/or part not performing satisfactorily may be returned to CWT for evaluation. A Return Goods Authorization (RGA)
number must first be obtained by either calling or writing your local authorized dealer, distributor or CWT direct, prior to shipping the
product. The problem experienced with the product and/or part must be clearly described. The RGA number must appear prominently
on the exterior of the shipped box(es). The product and/or part must be packaged either in its original packing material or in
comparable and suitable packing material, if the original is not available. You are responsible for paying shipping charges to CWT and
for any damages to the product and/or part that may occur during shipment. It is recommended that you insure the shipment for the
amount you originally paid for the product and/or part.
If, after the product and/or part is returned prepaid and evaluated by CWT, it proves to be defective while under warranty, CWT will,
at its election, either repair or replace the defective product and/or part and will return ship at lowest cost transportation prepaid to you
except for shipments going outside the 50 states of the United States of America. If upon inspection, it is determined that there is no
defect or that the damage to the product and/or part resulted from causes not within the scope of this limited warranty, then you must
bear the cost of repair or replacement of damaged product and/or part and all return freight charges. Any unauthorized attempt by the
end user to repair CWT manufactured products without prior permission shall void any and all warranties. For service, contact your
authorized dealer or distributor or CWT direct at (805) 549-9724.
Exclusive Warranty
There is no other expressed warranty on CWT products and/or parts. Neither this warranty, nor any other warranty, expressed or
implied,including any implied warranties or merchantability of fitness, shall extend beyond the warranty period. Some states do not
allow limitation on how long an implied warranty lasts, so that the above limitation or exclusion may not apply to you.
Disclaimer of Incidental and Consequential Damages
No responsibility is assumed for any incidental or consequential damages; this includes any damage to another product or products
resulting from such a defect. Some states do not allow the exclusion or limitation of incidental or consequential damages, so that
above limitation or exclusion may not apply to you.
Legal Remedies of Purchaser
This warranty gives you specific legal rights and you may also have other rights, which vary from state to state.
THIS STATEMENT OF WARRANTY SUPERSEDES ALL OTHERS PROVIDED TO YOU AT ANY PRIOR TIME.