The OSW-P-1001-MV is designed for offices up to 300 square feet. Coverage testing has been
performed according to the NEMA WD7 Guideline.
Maximum coverage area may vary somewhat according to room shape and the presence of
obstacles.
Location
When installing the OSW-P-1001-MV in a new junction box, choose the switch location
carefully to provide optimum coverage of the occupied area. When replacing an existing Wall
Switch, bear in mind that there must be a clear Line-of-sight between the sensor and the area to be
covered. Avoid pointing the OSW-P-1001-MV directly into the hallway where it may detect
passers-by.
The OSW-P-1001-MV can be installed in any standard single gang box. It may be installed in the
same manner as an ordinary Wall Switch.
• Wire the OSW-P-1001-MV as described in the wiring section.
• Mount the OSW-P-1001-MV in the junction box.
DIAGRAM 1A: SENSOR IN ONE LOCATION
Light Fixture
White
Neutral
Ground
Bare
Green
3-Way
Blue
Black
Hot
Black
120/277V
Hot
Black
Relay OUT
Red
120/277V
Orange
Relay IN
Installation Instructions
Model # OSW-P-1001-MV
Passive Infrared (PIR) Single Relay
Occupancy Sensing Wall Switch
• Read all instructions on both sides of this
sheet first
• Install in accordance with ALL local codes
• For indoor use only
General Information
Technology:
Passive Infrared (PIR)
Electrical Ratings:
120 VAC:
• Incandescent/Magnetic Low
Voltage/Magnetic Ballast – Max. load: 15A,
1800W, 60 Hz
• LED/Compact Fluorescent/Electronic Low
Voltage/Electronic Ballast – Max. load: 10A,
1200W, 60 Hz
Motor Load: ½ HP @ 125 VAC
277 VAC:
• Magnetic Low Voltage/Magnetic Ballast/
LED/Compact Fluorescent/Electronic Low
Voltage/Electronic Ballast – Max. Load:
8A, 2200W, 60 Hz
No Minimum Load Requirement
Time Delays:
selectable 5 seconds/test, 5
minutes (factory default), 10, and 30 minutes
Coverage:
Major motion – 1000 sq. ft.
Minor motion – 300 sq. ft.
Light Level Sensing:
0 to 200 foot-candles
Operating Environment:
• Temperature: 32° F – 104° F (0° C – 40° C)
• Relative Humidity: 20% to 90%
Non-condensing
Housing:
Durable, injection molded housing.
Polycarbonate resin complies with UL94VO
Size:
Mounting Plate/Strap Dimensions:
4.2" H x 1.8" W (106.5 mm x 46 mm)
Product Housing Dimensions:
2.87" H x 1.6" W x 1.42” D (72.8 mm x
40.7 mm x 36 mm)
LED Indicators:
Green LED indicates load status
and motion detection
Specifications
Description
The Occupancy Sensing Wall Switch can replace a standard Wall Switch in any of the following
applications:
• Single location – one Single Pole switch
• Two locations – one location is the sensor and the other location is a standard 3-way switch
• Two locations – replace both 3-way switches with sensors
In Automatic ON Mode, the lights turn ON automatically when a person enters the room. In
Manual ON Mode, the lights are turned ON by pressing the Pushbutton. In either mode, the
lights stay ON as long as the sensor detects motion in the room. When the room is vacated, the
lights turn OFF automatically after a preset Time Delay interval.
The Daylighting feature prevents lights from turning ON, when the room is adequately illuminated
by natural light.
Vacancy Mode
prevents motion from automatically turning on the lights upon initial activation.
To place the unit into vacancy mode, press and hold the ON/OFF button for 5 seconds until the
indicator LED blinks. Release the button while the LED is blinking. Repeat this procedure to
restore to normal automatic activation.
Override Mode
is used to turn OFF all motion sensing and allows the device to be used as a
regular ON/OFF switch or in the unlikely event of failure of the motion sensor. Press and hold the
ON/OFF button for 10 seconds until the LED indicator blinks for the second time (the LED will
also blink at the 5 second point). Release the button while the LED is blinking. Repeat this
procedure to restore normal operation.
ON/OFF Button Disable Mode
disables the ON/OFF button and sensor becomes automatic only
control regardless of the setting for automatic or manual activation. This feature will not allow
someone to turn light(s) OFF via the Pushbutton while people are in common areas such as
restroom, break room, and copy room areas. To place the unit into ON/OFF Button Disable
Mode, press and hold the ON/OFF button for 15 seconds until the LED indicator blinks for the
third time (the LED will also blink at the 5 seconds and 10 seconds point) and then release the
button while the LED is blinking. Repeat this procedure to restore normal operation.
Installation
Wiring
CAUTION:
Before installing or performing any service on a Greengate system, the power
MUST be turned OFF at the branch circuit breaker. According to NEC 240-83(d), if the
branch circuit breaker is used as the main switch for a fluorescent lighting circuit, the
circuit breaker should be marked “SWD”. All installations should be in compliance with
the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS:
The life of some compact
fluorescent lamps (CFLs) is shortened by frequent automatic or manual switching. Check with
CFL and ballast manufacturer to determine the effects of cycling.
1. Make sure power is turned OFF at the branch circuit breaker.
2. Wire units as shown in wiring diagrams per applicable voltage requirements.
3. Mount unit to Wall Box.
4. Turn power back ON at the branch circuit breaker and wait 30 seconds for the unit
to stabilize.
5. Make necessary adjustments. (See Checkout and Adjustments section)
6. Install Wall Switch plate.
First Location Second Location
DIAGRAM 2A: SWITCH IN LOCATION WITH HOT WIRE
3-Way Switch
Hot
Black
120/277V
Hot
Black
120/277V
Black
3-Way
Blue
Neutral
Neutral
White
White
Light
Fixture
Black Traveler
Red Traveler
Red
Relay OUT
Ground
Bare
Green
Relay IN
Orange
Coverage
0
15’
MAJOR MOTION
1000 SQ. FT.
36’
0
COVERAGE PATTERN
MINOR MOTION
300 SQ. FT.
8’
15’
8’
15’
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns
Minor Motion, IR
Major Motion, IR
Cooper Lighting Solutions
1121 Highway 74 South Peachtree City, GA 30269
P:770-486-4800
www.cooperlighting.com