FIRE
4098 Detectors, Sensors, and Bases
Application Manual
574-709
Rev. T
ii
iii
© 2008- 2011 SimplexGrinnell LP. All rights reserved.
Specifications and other information shown were current as of publication and are subject to
change without notice.
Suffix “C” or “CA” following an eight-digit Product ID number denotes ULC-listed product.
Suffix “E” following an eight-digit Product ID number denotes Global product. The second suffix
identifies market country, models with this suffix are not UL Listed.
Tyco, IDNet
, Simplex and the Simplex logo are trademarks of Tyco International Ltd. and its
affiliates and are used under license.
MAPNET II
Communication Net is protected by US Patent No. 4,796,025.
TrueAlarm
Analog Detection is protected by US Patent No. 5,155,468.
TrueAlarm
Detector Base is protected by US Patent No. 5,173, 683.
All illustrations of actual detectors, sensors, and bases shown in this publication are artist’s renditions.
Copyrights and Trademarks
Copyrights
Trademarks
iv
Cautions and
Warnings
READ AND SAVE THESE INSTRUCTIONS- Follow the instructions in this installation
manual. These instructions must be followed to avoid damage to this product and associated
equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX® PRODUCT THAT APPEARS DAMAGED- Upon
unpacking your Simplex product, inspect the contents of the carton for shipping damage. If
damage is apparent, immediately file a claim with the carrier and notify an authorized
Simplex product supplier.
ELECTRICAL HAZARD - Disconnect electrical field power when making any internal adjust-
ments or repairs. All repairs should be performed by a representative or authorized agent of
your local Simplex product supplier.
STATIC HAZARD - Static electricity can damage components. Handle as follows:
Ground yourself before opening or installing components.
Prior to installation, keep components wrapped in anti-static material at all times.
FCC RULES AND REGULATIONS – PART 15 - This equipment has been tested and
found to comply with the limits for a Class A digital device pursuant to Part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in
accordance with the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own
expense.
Cautions and Warnings
v
Copyrights and Trademarks ........................................................................................... iii
Copyrights ................................................................................................................... iii
Trademarks ................................................................................................................. iii
Cautions and Warnings .................................................................................................. iv
Table of Contents ............................................................................................................ v
Chapter 1 Overview .............................................................................. 1-1
Introduction .............................................................................................................. 1-1
In this Chapter ......................................................................................................... 1-1
Special Considerations ................................................................................................ 1-2
Overview .................................................................................................................. 1-2
Special Considerations for Smoke Detectors and Sensors ..................................... 1-2
Smoke Detector/Sensor Applications ...................................................................... 1-2
Where to Place Detectors and Sensors ...................................................................... 1-3
Proper Locations for Detectors and Sensors ........................................................ 1-3
Where Not to Place Detectors and Sensors ................................................................ 1-6
Improper Locations for Detectors and Sensors ....................................................... 1-6
Principles of Operation ................................................................................................ 1-8
Introduction .............................................................................................................. 1-8
Heat Detector Operation .......................................................................................... 1-8
Photoelectric Smoke Detectors/Sensors ................................................................. 1-8
Ionization Smoke Detectors/Sensors ...................................................................... 1-8
Carbon Monoxide Gas Detectors/Sensors .............................................................. 1-8
Chapter 2 4098 Smoke Detectors, Heat Detectors and Bases .......... 2-1
Introduction .............................................................................................................. 2-1
In this Chapter ......................................................................................................... 2-1
4098 Smoke Detectors ................................................................................................ 2-2
Introduction .............................................................................................................. 2-2
Smoke Detector Limitations ..................................................................................... 2-2
Specifications ........................................................................................................... 2-3
Mounting Requirements ........................................................................................... 2-4
4098 Heat Detectors .................................................................................................... 2-5
Introduction .............................................................................................................. 2-5
Heat Detector Types ................................................................................................ 2-5
Specifications ........................................................................................................... 2-5
4098 Bases .................................................................................................................. 2-8
Introduction .............................................................................................................. 2-8
Mounting .................................................................................................................. 2-9
Wiring ..................................................................................................................... 2-10
Chapter 3 TrueAlarm Sensors, Sensor Bases, and QuickConnect
Smoke Sensors .................................................................................... 3-1
Introduction .............................................................................................................. 3-1
Table of Contents
vi
In this Chapter ......................................................................................................... 3-1
4098 TrueAlarm Sensors ............................................................................................. 3-2
Specifications ........................................................................................................... 3-2
Special Applications ................................................................................................. 3-2
Mounting .................................................................................................................. 3-2
4098 TrueAlarm Sensor Bases ................................................................................... 3-3
Introduction .............................................................................................................. 3-3
Specifications ........................................................................................................... 3-3
Setting the Base’s Address...................................................................................... 3-3
Address Setting for the 2120 CDT System.............................................................. 3-5
Address Setting for the 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 System3-5
Multi-Sensor Bases 4098-9795 and 4098-9796 ..................................................... 3-7
Wiring ....................................................................................................................... 3-7
4098 TrueAlarm QuickConnect Smoke Sensors ....................................................... 3-12
Overview ................................................................................................................ 3-12
Specifications ......................................................................................................... 3-12
Setting the Sensor’s Address ............................................................................... 3-13
Wiring ..................................................................................................................... 3-14
Chapter 4 Accessories ......................................................................... 4-1
Introduction .............................................................................................................. 4-1
In this Chapter ......................................................................................................... 4-1
Relay Module Accessories .......................................................................................... 4-2
2098-9737 Relay Module Wiring ............................................................................ 4-2
4098-9822 Relay Module Wiring ............................................................................. 4-3
Relay Module Installation......................................................................................... 4-4
Remote LED Module ............................................................................................... 4-4
Chapter 5 Compatibility and Testing .................................................. 5-1
Introduction .............................................................................................................. 5-1
In this Chapter ......................................................................................................... 5-1
Compatibility ................................................................................................................ 5-2
Compatibility for 4098 Detectors and Detector Bases ............................................. 5-2
Maintenance and Testing ............................................................................................ 5-4
Maintenance ............................................................................................................ 5-4
Preferred Method of Testing Smoke Detectors/Sensors ......................................... 5-4
Test Equipment Available ........................................................................................ 5-4
Alternate Method for Testing Sensors ..................................................................... 5-5
Magnetic Test for Photoelectric Detectors ............................................................... 5-5
Magnetic Test for Ionization Detectors .................................................................... 5-7
Ion Detector Sensitivity Test .................................................................................... 5-7
Cleaning ....................................................................................................................... 5-8
Introduction .............................................................................................................. 5-8
Photoelectric Smoke Detector/Sensor Cleaning ..................................................... 5-8
Special Considerations for Ion Detectors and Sensors ........................................... 5-8
Trouble Indications ...................................................................................................... 5-9
Trouble Indications for TrueAlarm Sensors ............................................................. 5-9
Trouble Indications, Continued .................................................................................. 5-10
vii
Fire Alarm Trouble and Maintenance Log ................................................................. 5-11
Fire Alarm Trouble and Maintenance Log ............................................................ 5-11
Index ............................................................................................................................. I-1
1-1
The purpose of this publication is to provide information concerning the proper application of both
heat and smoke detectors/sensors in conjunction with fire alarm systems.
The information in this publication is intended to be used only as a technical guide. The
requirements of applicable codes and standards, as well as directives of Authorities Having
Jurisdiction (AHJ’s), should be followed.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Special Considerations 1-2
Where to Place Detectors and Sensors 1-3
Where Not to Place Detectors and Sensors 1-6
Principles of Operation 1-8
Chapter 1
Overview
Introduction
In this Chapter
1-2
Before installing detectors/sensors, make a survey of the area to be covered in accordance with
information provided in NFPA 72, (an excerpt of which is provided in the “Smoke Detector/
Sensor Applications” section below). For additional information, refer to NFPA 72 and the
NEMA Guide for Proper Use of System Smoke Detectors.
Is there human occupancy?
Contents to be protected.
Type of construction and use.
Burning characteristics of contents.
Air movement - stratification.
Deflections and obstructions.
Height of ceilings.
Surface conditions of ceilings.
Type of ceiling construction.
Total area.
Vent locations - velocities - dilution.
Each detector/sensor is capable of providing up to 900 square feet (84 square meters) of coverage,
depending on the following:
Requirements of local codes.
Results of engineering evaluation.
Special Considerations
Overview
Special
Considerations for
Smoke Detectors
and Sensors
Smoke
Detector/Sensor
Applications
1-3
IMPORTANT: The guidelines in this section are adapted from standards
published by the National Fire Protection Association, Quincy,
Massachusetts, U. S. A. These standards include NFPA 72,
“National Fire Alarm Code”; NFPA 70, “National Electrical Code”,
Article 760; and NFPA 90A, “Standard for the Installation of
Air Conditioning and Ventilating Systems.”
To provide effective early warning of a developing fire situation, smoke detectors/sensors should
be installed in all areas of the protected premises. Total coverage as defined by NFPA 72 should
include all rooms, halls, storage areas, basements, attics, lofts, and spaces above suspended
ceilings including plenum areas utilized as part of the HVAC system. In addition, this should
include all closets, elevator shafts, enclosed stairways, dumbwaiter shafts, chutes and other
subdivisions and accessible spaces.
Fire detection systems installed to meet local codes or ordinances may not be adequate for early
warning of the fire. Some codes or ordinances have minimum objectives such as capturing
elevators or preventing circulation of smoke through HVAC systems instead of early detection of
fire.
You should weigh the costs against the benefits of installing a complete fire detection system
when any detection system is being installed. The location, quantity and zoning of
detectors/sensors should be determined by what objectives are desired rather than the minimum
requirements of any local codes or ordinances.
Detectors/sensors may be omitted from combustible blind spaces when any of the following
conditions prevail:
Where the ceiling is attached directly to the underside of the supporting beams of a
combustible roof or floor deck.
Where the concealed space is entirely filled with noncombustible insulation. (In solid joist
construction, the insulation need only fill the space from the ceiling to the bottom edge of the
joist of the roof or floor deck.)
Where there are small concealed spaces over rooms, provided the space in question does not
exceed 50 square feet (4.6 square meters).
In spaces formed by sets of facing studs or solid joists in walls, floors, or ceilings where the
distance between the facing studs or solid joists do not exceed 6 inches (15 cm).
Detectors/sensors may also be omitted from below open grid ceilings where all of the following
conditions are met:
The openings of the grid are at least 1/4 inch (6 mm) in the smallest dimension.
The thickness of the material does not exceed the smallest of the grid openings.
The openings constitute at least 70% of the area of the ceiling material.
Continued on next page
Where to Place Detectors and Sensors
Proper Locations
for Detectors
and Sensors
1-4
Detectors/sensors are usually required or recommended underneath open loading docks or
platforms and their covers, and in accessible under-floor areas in buildings without basements.
Detectors/sensors may be omitted from combustible blind spaces when all of the following
conditions prevail:
1. The space is not accessible for storage purposes, it is protected against the entrance of
unauthorized persons, and it is protected against the accumulation of windblown debris.
2. The space contains no equipment/structures (such as steam pipes, electrical wiring, ducts,
shafts, or conveyors) that could potentially ignite or conduct the spread of fire.
3. The floor over the space is tight.
4. Non flammable liquids are processed, handled, or stored on the floor above the space.
“Total coverage” as described in NFPA 72, is the definition of a complete fire detection system.
In some of the specified areas of coverage, such as attics, closets, under open loading docks or
platforms, a heat detector may be more appropriate than a smoke detector. Careful consideration
should be given to the detector manufacturer’s instructions and the following recommendations in this
guide.
In general, when only one detector/sensor is required in a room or space, the detector/sensor should
be placed as close to the center of the ceiling as possible. Central location of the detector/sensor is
best for sensing smoke and/or fire in any part of the room. If a center location is not possible, it may
be placed no closer than 4 inches (10 cm) from the wall, or if listed for wall mounting, it may be
mounted on the wall. Wall mounted detectors/sensor should be located approximately 4 to 12 inches
(10 to 30 cm) from the ceiling to the top of the detector, and at least 4 inches (10 cm) from any
corner wall junction (see the figure below).
FigureTag FD4-709-01
4 in
(10 cm)
Minimum
12 in
(30 cm)
Maxi mum
Never her e
Top of t he detect or
acceptabl e here
Side
wall
Accept abl e here
Ceiling
Not e:
Measurements shaown are to the
cl osest edge of the detect or.
4 in
(10 cm)
Figure 1-1. Wall and Ceiling Mounted Detector/Sensor
Continued on next page
Where to Place Detectors and Sensors,
Continued
Proper Locations
for Detectors
and Sensors
Note: Measurements shown are to the
closest edge of the detector.
1-5
When an air supply and/or an air return duct opening is present in a room or space, the
detector/sensor(s) should be placed in the path of the air flow toward the return air duct opening
(see below).
FigureTag FD4-709-02
Retur
n
air
Correct
Suppl
y
air
Incor r ect
Figure 1-2. Detector Placement - Air Supply and/or Return Ducts
Smoke tests are helpful in determining proper placement. Special attention should be given
to smoke travel directions and velocity, since either can affect detector/sensor performance.
Placement of a detector/sensor near air conditioning or incoming air vents can also cause
excessive accumulation of dust and dirt on the detector/sensor. This dirt can cause the
detector/sensor to malfunction and cause nuisance alarms. Detectors/sensors should not be located
closer than 3 feet (0.9 m) from an air supply diffuser.
Spot type detectors/sensors in properly engineered systems, may also be placed in return air ducts, or
in approved duct detector housings designed for this application. Although duct detectors are not a
substitute for open area detectors, they can provide an effective method of initiating building control
functions to prevent smoke from being transported from the fire area to other parts of a building.
Where to Place Detectors and Sensors,
Continued
Proper Locations
for Detectors
and Sensors
1-6
One of the major causes of nuisance alarms is improper placement of detectors/sensors.
The best way to avoid nuisance alarms is to not install detectors/sensors in environments that can
cause them to malfunction. See the table and examples provided below.
Table 1-1. Environmental Conditions that Influence Detector Response*
Detection
Protection
Air Velocity
>300 ft.
(91.4m)/min.
Atm. Pressure
3000 ft. (914m)
Above Sea Level
Humidity
>93% RH
Temp. <32°F (0C)
>100°F (38C)
Color of
Smoke
Ion X X X X O
Photo O O X X X
Beam O O X X O
Air Sampling O O X X O
* See Table A-5-3.6.1.1 in NFPA 72
X = May affect detector/sensor response
O = Generally does not affect detector/sensor response
DO NOT PLACE DETECTORS/SENSORS:
In excessively dusty or dirty areas, such as feed rooms, steel mills, etc. Dust and dirt can
accumulate on the detector/sensor’s sensing chamber and make it overly sensitive, or block
the air entrances to the sensing chamber and make the detector/sensor less sensitive to smoke.
Be especially careful to avoid areas where fumigants, fog or mist-producing materials, or
sweeping and cleaning compounds are used. These substances may cause nuisance alarms.
Outdoors, in stables, open storage sheds, or other open structures affected by dust,
air currents, or excessive humidity and temperature.
In damp or excessively humid areas, or next to bathrooms with showers. Water droplets
can accumulate inside the sensing chamber and make the detector/sensor overly sensitive.
A tremendous amount of humid air is produced during a hot shower. The moisture in this
humid air can enter the sensing chamber as water vapor, then cool and condense into droplets
that can cause a nuisance alarm.
In elevator lobbies over ashtrays or where people smoke while waiting for the elevator.
In very cold or very hot environments, or in unheated buildings or rooms where the
temperature can fall below or exceed the operating temperature range of the detector/sensor.
At temperatures below 32° F (0° C), ice crystals or condensation can appear inside the sensing
chamber and make it overly sensitive or cause a nuisance alarm. At temperatures above the
operating range of the detector/sensor greater than 120° F (49° C), its internal components
may not function properly.
In or near areas where combustion particles are normally present, such as in kitchens or other
areas with ovens and burners; in garages, where particles of combustion are present in vehicle
exhausts; within 15 feet (4.5 meters) of any type of furnace, hot water heater, or gas space
heater; or in welding shops or other types of work areas where some form of combustion is
used in the activity normally conducted in that area. When a detector must be located in or
adjacent to such an area, a fixed temperature heat detector may be appropriate.
Continued on next page
Where Not to Place Detectors and Sensors
Improper Locations
for Detectors
and Sensors
1-7
In air streams passing by or through kitchens. Air often enters a residence or a residential unit
of an apartment building through cracks around the front and/or back doors. If the air return
is in the bedroom hallway or in the bathroom, and if air from the kitchen easily enters the air
stream going from the door to the air return, combustion particles from cooking can cause
nuisance alarms. Install detectors/sensors so that they protect the bedrooms, but so they are
out of the air stream.
In or near manufacturing areas, battery rooms, or other areas where substantial quantities of
vapors, gases or fumes may be present. Strong vapors, like excessive humidity, can make
detectors/sensors overly sensitive or less sensitive than normal. In very large concentrations,
gases heavier than air, such as carbon dioxide, may make detectors/sensors more sensitive,
while gases lighter than air, such as helium, may make them less sensitive. Aerosol particles
may collect on detector/sensor chamber surfaces and cause nuisance alarms.
Insect-infested areas. If insects enter a detector/sensor’s sensing chamber, they can cause a
nuisance alarm. Take proper insect eradication procedures before installing detectors/sensors
in such locations. If spraying is done, do not allow insect spray to enter the detectors/sensors.
Near fluorescent light fixtures. Electrical noise generated by fluorescent light fixtures may
cause nuisance alarms. Install detectors/sensors at least 1 foot (0.3 meters) away from such
light fixtures.
When using the CO Base for CO fire detection, do not install in locations that could have
potentially high non-fire levels of CO.
Underwriters Laboratories (UL) has three standards for smoke detectors: one for duct
detectors/sensors, UL 268A; one for single and multiple station detectors/sensors, UL 217; and
one for system type detectors/sensors, UL 268. Detectors/sensors should only be used in the
applications for which they are specifically listed.
The NFPA 101 Life Safety Code states that single station smoke detectors shall sound an
alarm only within an individual living unit or similar area and shall not actuate the building
fire alarm system. It also states, “All systems and components shall be approved for the
purpose for which they are installed.”
In addition to possible code noncompliance, the following deficiencies would exist in a series
of residential smoke detectors connected in a fire alarm system mode:
Since the fire alarm system is not supervised, vandals or others could disconnect a detector or
the entire system, leaving a building without protection. The residents would be unaware of
the serious life threatening condition.
Residential detectors do not latch in alarm. In other words, the detector self-resets. One
detector in alarm sounds all the detectors connected together. It would be difficult to
identify or locate a specific detector that initially put the system into alarm after the alarm
condition was cleared.
System detectors/sensors latch in alarm. They do not reset until power is momentarily
disconnected. This makes it convenient to identify the location of the detector/sensor that caused
the control panel to alarm. In addition, system detectors are specifically designed to connect to a
supervised control panel. Two-wire detectors require a UL compatibility review to verify that the
detector and panel properly operate together. A typical life safety fire alarm system for an
apartment complex would be to use system detectors/sensors and manual fire alarm stations in the
hallways and common areas of the complex and residential single station type detectors and heat
detectors in the individual apartments. The system detectors/sensors, manual stations and heat
detectors would be connected to a supervised control panel, sound a general alarm and
automatically notify the proper authorities that a fire condition exists. The residential detectors
located in the apartments would be interconnected only within the individual living quarters of
each apartment. These residential units would sound an alarm only in the apartment unit.
Where Not to Place Detectors and Sensors,
Continued
Improper Locations
for Detectors
and Sensors
1-8
This section describes how the different types of detectors and sensors work. For additional
information on TrueAlarm sensor operation, refer to the TrueAlarm Concepts publication
(PER-91-024).
The heat detector senses the heat or the Rate-of-Rise (ROR) in the air temperature of the
environment in which it is located. The heat detector is comprised of electronic circuitry and a
mechanical package that is designed to sense the ROR of the air temperature in an expedient and
reliable fashion. Upon detection of an abnormal increase in air temperature, or ROR in air
temperature, the electronics indicate an alarm by increasing the amount of current draw from the
monitor zone it is connected to. The monitor zone is a supervised detection circuit that is tied
back to a main control panel that takes appropriate action to indicate an alarm has been reported,
if the zone current is substantially increased.
Being of an electronic design, the temperature of the air is sensed by using two negative
temperature coefficient thermistors. The resistance of the thermistors goes down with an increase
in temperature. One thermistor is placed in a position such as to sense the open air temperature
very rapidly (RT1). The second thermistor is positioned in a small cavity that protrudes out from
the main body of the detector (RT2). The location of RT2 allows for fast detection of a quick
change in the air temperature, but yet for a slow or medium rate of temperature change, the
detector does not trip due to the ROR feature. For a slower change in temperature, the detector
trips into alarm due to a set fixed temperature that is sensed by RT1. For a fast temperature rise,
when a difference in temperature sensed by RT1 and RT2 has reached a predetermined amount,
the detector trips into alarm.
These devices operate on a light scattering principle. The smoke sensing chamber contains an
infrared LED source with a peak spectral emission of 880 nanometers. This source is placed at an
angle from a spectrally matched photodiode receiver. During a NO SMOKE condition, only light
reflected from the chamber walls enters the receiver and shows up as a small photocurrent. As
smoke particles enter the sensing chamber and cross the light beam of the LED, more light reaches
the receiver due to scattering. The receiver circuitry converts this photocurrent into a signal
voltage. In a detector, when this voltage reaches a preset level, an alarm is produced. In a sensor,
this signal voltage goes into an 8-bit, A to D (analog to digital) converter. A digital representation
of this signal voltage is then transmitted to the fire alarm panel for further processing.
These devices use a small radiation source, Americium-241, which emits alpha particles that
ionize air molecules between two electrically charged electrodes. With the application of a
DC voltage .to these electrodes, a small ionization current flows within the chamber. As smoke
enters the chamber, a decrease in ionization current results. This current is converted into a signal
voltage by a transimpedance circuit. In a detector, when this signal voltage drops below a preset
level, an alarm is produced. In a sensor, this signal voltage goes into an 8-bit A to D (analog to
digital) converter. A digital representation of this signal voltage is then transmitted to the fire
alarm panel for further processing.
The CO Sensor and Sounder Bases with a CO Replaceable Sensor (CRS) module work in
conjunction with existing detector heads. The CO Sensor Base enhances fire detection and
provides the ability to combine fire and toxic gas leakage detection in a single device. The CO
sensor measures the concentration of carbon monoxide gas in the air in part per million (PPM).
When toxic gas operation is selected, the FACP panel may generate either a supervisory, utility or
priority 2 alarms. The alarm level is calculated within the panel based on the time integrated CO
levels that have been measured at the detector.
Principles of Operation
Introduction
Heat Detector
Operation
Photoelectric Smoke
Detectors/Sensors
Ionization Smoke
Detectors/Sensors
Carbon Monoxide
Gas
Detectors/Sensors
2-1
This chapter contains specification and mounting information for 4098 Smoke Detectors,
Heat Detectors, and Bases.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
4098 Smoke Detectors 2-2
4098 Heat Detectors 2-5
4098 Bases 2-8
Chapter 2
4098 Smoke Detectors, Heat Detectors and Bases
Introduction
In this Chapter
2-2
CAUTION: Install the detectors described in this publication in accordance with
applicable NFPA standards, local codes, and the Authorities Having
Jurisdiction (AHJs). Failure to follow these instructions may result in
failure of the detector to initiate an alarm condition. The manufacturer
is not responsible for detectors that have been improperly installed,
tested, or maintained.
The smoke detectors used with these bases are designed to activate and initiate emergency action,
but do so only when used in conjunction with other equipment. They are designed for installation
in accordance with NFPA 72 National Fire Alarm Code.
Smoke detectors do not work without power. AC or DC powered smoke detectors do not
work if the power supply is cut off for any reason.
Smoke detectors do not sense fires when smoke does not reach the detectors. Smoke from
fires in chimneys, in walls, on roofs or on the other side of closed doors may not reach the
smoke detector and alarm it.
A detector may not detect a fire developing on another level of a building. For this reason,
detectors should be located on every level of a building.
Smoke detectors have sensing limitations. Ionization detectors are better at detecting fast,
flaming fires than slow, smoldering fires. Photoelectric detectors sense smoldering fires
better than flaming fires. Because fires develop in different ways, and are often unpredictable
in their growth, neither type of detector is always best, and a given detector may not always
provide warning of a fire. In general, detectors cannot be expected to provide warning for
fires resulting from inadequate fire protection practices, violent explosions, escaping gases,
improper storage of flammable liquids like cleaning solvents, other safety hazards, or arson.
Smoke detectors cannot last forever. Smoke detectors contain electronic parts. Even though
detectors are made to last for many years, any of these parts could fail at any time. Therefore,
test your smoke detector system per NFPA 72 at least annually. Clean and take care of your
smoke detectors regularly. (See Chapter 5 of this publication for cleaning instructions.)
Continued on next page
4098 Smoke Detectors
Introduction
Smoke Detector
Limitations
2-3
Table 2-1. Smoke Detector Specifications
Specifications Smoke Detector Data
Detector
PID (4098)
-9601, -9605 -9602 -9603
Type of Detector
Photoelectric
Photoelectric
with Heat
Ionization
Working Voltage
(2-wire)
8.5 – 33 VDC 8.5 – 33 VDC 8.5 – 33 VDC
Rated Voltage
(4-wire)
15 – 32 VDC 15 – 32 VDC 15 – 32 VDC
Input Ripple
Voltage
25% Max. 25% Max. 25% Max.
Max. Alarm
Current
86 mA 86 mA 86 mA
Surge Current
<200 A <200 A <200 A
Standby Current
<100 A <100 A <100 A
Heat Element
Rating
N/A
135 F
N/A
Humidity Range
(Non-Condensing)
10-95% RH 10-95% RH 10-95% RH
Air Velocity
Range
0-2000 FPM 0-2000 FPM 0-200 FPM
Continued on next page
4098 Smoke Detectors,
Continued
Specifications
2-4
All smoke detectors identified in Table 2-1 mount to a detector base (refer to the “4098 Bases”
section of this chapter for more information). Use the following considerations and Figure 2-1
when mounting smoke detectors.
IMPORTANT: Smoke must enter the chamber of the detector. Thus, air flow, air
stratification, air velocity, air stagnation, and air migration affects
detector efficiency.
Note: Where the possibility of positive airflow from the electrical conduit/junction box exists,
seal the conduit openings with 3M Weatherban #606 (or equivalent), a non-flammable
sealing compound.
Do not install detectors in areas where temperatures are likely to exceed 100 F (38 C)
or fall below 32 F (0 C).
Because the 4098-9602 detector combines heat sensing, DO NOT install this detector in
locations where the ambient temperatures exceed 100 F (38 C) or where temperature
fluctuations above 6 F/min. occur.
Do not install detectors on a ceiling within 4 inches (10 cm) of a wall.
Do not install detectors where forced air ventilation may dilute the smoke before it
reaches the detector.
Do not install detectors in areas where smoke is normally present (kitchens, furnace
rooms, laundry rooms, loading docks, rooms with fireplaces, rooms with candles,
soldering rooms, etc.).
Do not install detectors in areas where there is likely to be steam (in hospital patient
rooms with vaporizers, near shower rooms, above large sinks, etc.).
Do not install detectors above ashtrays in elevator lobbies.
Wall-mounted detectors should be located 4 to 12 inches (10-30.5 cm) from the ceiling to
detector head.
Protect all detector heads during construction to avoid infiltration of construction debris.
Remove any protective covers before activating the system.
If using the adapter plate, tighten the mounting screws without warping the adapter plate.
4098 Smoke Detectors,
Continued
Mounting
Requirements
2-5
This section contains general notes, specifications, and mounting information for the heat
detectors shown in Table 2-2.
WARNING: Heat detectors are NOT life-safety devices; USE HEAT DETECTORS
FOR PROPERTY PROTECTION ONLY! For life-safety requirements,
use smoke detectors.
Notes:
For all heat detectors, provide electronic supervision with battery back-up at the fire alarm
control panel.
Where the possibility of positive airflow from the electrical conduit/junction box exists, seal
the conduit openings with 3M Weatherban #606 (or equivalent), a non-flammable sealing
compound.
Refer to NFPA 72 for application, test, and maintenance requirements.
Fixed Temperature Heat Detectors:
Electronic fixed temperature heat detectors use a fast response, thermistor based design to provide
temperature sensing that quickly, accurately, and consistently identifies when fixed temperatures are
exceeded. For this reason, the fixed temperature detectors are recommended for most applications.
With a UL spacing distance of 60 X 60 feet, the fixed temperature electronic heat detectors replace
both mechanical fixed as well as mechanical ROR heat detectors.
ROR Temperature Heat Detectors:
Electronic Rate-of-Rise (ROR) heat detectors detect fixed temperature alarm thresholds the same as
the fixed temperature heat detectors, plus detect a ROR alarm with a patented ROR detection design
that can quickly respond to sudden temperature variations. Due to the nature of the fast response to
temperature changes, care must be taken for proper installation of ROR heat detectors. ROR heat
detectors should be installed in stable environmentally controlled areas. These detectors must not be
installed where hot or cold air can be blown on them (near ductwork, industrial equipment, air vents
etc.). ROR detectors should not be installed where more then 6 F per minute temperature changes
can normally occur.
Features:
Rate-of-Rise and Fixed Temperature (see Table 2-2)
Alarm LED
Compatible with 2-Wire Initiating Device Circuits
Current-Limited Alarm State
Electrical Specifications:
Typical Standby Current - 80 Microamps
Typical Alarm Current - 40 Milliamps
Maximum Current - 80 Milliamps while in alarm state
Operating Range - 15-32 VDC
Maximum Ripple Voltage Allowed - 30%
Continued on next page
4098 Heat Detectors
Introduction
Heat Detector Types
Specifications
2-6
Table 2-2. Heat Detector Models and Features
Detector Model Rating or Class*
Area /
Language
Color Code
4098-9612 (UL)
135 F (57 C) FT
English
4098-9613 (UL)
135 F (57 C) FT and RR
English
4098-9614 (UL)
200 F (93 C) FT
English White
4098-9615 (UL)
200 F (93 C) FT and RR
English White
4098-9616E A1 European Green
4098-9617E C European Red
4098-9618E A Australian White
4098-9619E B Australian Blue
4098-9621E D Australian Red
4098-9622E I Chinese Green
4098-9624E
134 F (56.7 C) FT
Korean
4098-9625E
134 F (56.7 C) FT and RR
Korean
4098-9626E
134 F (56.7 C) FT
Taiwanese
4098-9627E
134 F (56.7 C) FT and RR
Taiwanese
4098-9628E
190 F (87.8 C) FT
Korean
4098-9629E
190 F (87.8 C) FT and RR
Korean
4098-9630E
190 F (87.8 C) FT
Taiwanese
4098-9631E
190 F (87.8 C) FT and RR
Taiwanese
* RR abbreviates Rate-of-Rise; FT abbreviates Fixed-Temperature.
Continued on next page
4098 Heat Detectors,
Continued
Specifications
2-7
All heat detectors identified in the table below mount to a detector base (refer to the “4098 Bases”
section of this publication for more information). Use the information in Figure 2-1 when
mounting.
Table 2-3. Heat Detector Specifications
Product ID Description Application
Max. Spacing
Allowed (UL)
FM
4098-9612
Fixed-Temp. Only,
135 F (57 C)
Unusually violent
temp. fluctuations
and ceiling
temperatures not
exceeding
100 F (38 C)
70 X 70 ft
(21 X 21 m)
RTI = Quick
20 X 20 ft
(6.1 X 6.1 m)
4098-9613
Fixed-Temp. and
Rate-of-Rise,
135 F (57 C)
Normal temp.
fluctuations
and ceiling
temperatures not
exceeding 100 F
(38 C)
70 X 70 ft
(21 X 21 m)
RTI = Quick
20 X 20 ft
(6.1 X 6.1 m)
4098-9614
Fixed-Temp. Only,
200 F (93 C)
Unusually violent
temp. fluctuations
and ceiling
temperatures
exceeding 100 F
(38 C) but not
150 F (68 C)
70 X 70 ft
(21 X 21 m)
RTI = Quick
20 X 20 ft
(6.1 X 6.1 m)
4098-9615
Fixed-Temp. and
Rate-of-Rise,
200 F (93 C)
Normal temp.
fluctuations
and ceiling
temperatures
exceeding 100 F
(38 C) but not
150 F (68 C)
70 X 70 ft
(21 X 21 m)
RTI = Ultra Fast
50 X 50 ft
(15.2 X 15.2 m)
4098 Heat Detectors,
Continued
Specifications
2-8
The 4098-9788 base is designed to be used with 4098 Series smoke and heat detectors, as well as
the QuickConnect2 photo sensor. To use a 4-wire configuration, you must use the 4098-9682
relay base. Heat detectors require the 4098-9684 base when used with a remote LED. This
section only covers the information necessary to mount and wire these base configurations.
Before installing these bases, make a survey of the area to be covered in accordance with
information provided in NFPA 72. For additional information, refer to the NEMA Guide for
Proper Use of System Smoke Detectors.
CAUTION: Install the bases in this section in accordance with applicable NFPA
standards, local codes, and Authorities Having Jurisdiction (AHJs).
Failure to follow these instructions may result in failure of the detector
to initiate an alarm condition. The manufacturer is not responsible for
detectors that have been improperly installed, tested, or maintained.
Continued on next page
4098 Bases
Introduction
2-9
The 4098-9788 base mounts to a 4-inch octagonal, 4-inch square, or single gang electrical box.
When mounting to a 4-inch square or any surface mounted box, the 4098-9832 adapter plate kit
must be used.
Figure 2-1. Typical Detector/Sensor Mounting
Notes:
1. Break off plastic lock tab to engage locking mechanism. To lock detector/sensor into base,
turn unit until the locking tab clicks into place. To unlock detector/sensor, insert the blade of a
screwdriver into this slot and then pull down on handle. This action allows the detector/sensor
to be turned and removed (see Figure 2-1).
2. Refer to the “Compatibility and Testing” chapter of this publication for detailed information
on compatible detectors/sensors.
3. Bases with relay modules require a 1 ½-inch extension ring (not supplied) mounted to the
4-inch square or octagonal electrical box to meet the space requirement of the relay cube and
its wires. The relay module(s) cannot be used in single-gang electrical box installations. The
relay cube 4098-9822 must be installed in the electrical box directly behind the sensor base.
4. Use Adapter Plate Kit 4098-9832 when mounting the 4098-9794 and 4098-9795 to a surface
mounted 4-inch square or octagonal box. Adapter plates must be installed with textured side
towards the electrical box for this installation only.
Continued on next page
4098 Bases,
Continued
Mounting
2-10
All screw terminals accommodate 14 to 18 AWG solid or stranded wire. When tightening
screws, the range of torque is 8 to 12 in-lbs. Connect wiring to the terminals shown in the figure
below. (Figures 2-2 through 2-6 show typical wiring applications for the 4098 bases.)
CAUTION: Do not loop wire under terminals. Break wire run to provide
supervision of connections.
2
1
3
4
Figure 2-2. Wiring and Mounting the Bases
FigureTag FD4-709-03
Notes:
1. Break off plastic tab where indicated to engage locking mechanism.
2. Once locking mechanism is engaged, you must insert a flat-head screwdriver in slot
indicated to release the detector from the base.
3. Use the slotted hole indicated for the first screw when mounting the base.
Continued on next page
4098 Bases,
Continued
Wiring
See Note 2
See Note 1
See Note 3
2-11
BACKUP 2
(SEE NOTE 3)
PRIMARY 1
(SEE NOTE 3)
LISTED
SIMPLEX
FIRE ALARM
CONTROL
PANEL
2120,
4001, 4002
4020, 4100+, 4100U,
4100ES, 4004, 4005 OR
4006
+
+
-
-
(SEE NOTE 4)
EOL
RESISTOR
(IF USED)
(SEE NOTE 2)
INITIATING
CIRCUIT
2
1
3
4
2
1
3
4
2
1
3
4
BLKRED
REMOTE LED
4098-9830
(SEE NOTE 1)
BLKRED
REMOTE LED
4098-9830
(SEE NOTE 1)
4098-9788
BASE
4098-9788
BASE
4098-9788
BASE
(SEE NOTE 5 ) (SEE NOTE 5 ) (SEE NOTE 5)
FigureTag FD4-709-04
Figure 2-3. 4098-9788 Base Connections for Style B or D Initiating Circuits
Notes:
1. If used, 4098-9830 Remote LED is polarized. Refer to Figure 2-6 to wire remote LED to the
Heat Detector; observe color-coded wiring.
2. Refer to wiring diagrams provided with system panel for proper End-Of-Line (EOL) resistor
value.
3. It is recommended that the Primary-1 and the Backup-2 lines be in separate wire runs and
in compliance with local requirements.
4. For Style D initiating circuit, wire per dotted lines and do not use EOL resistor.
5. Break wires before connecting to Terminal 4 to maintain supervision. Do not loop wire
underneath Terminal 4.
Continued on next page
4098 Bases,
Continued
Wiring
2-12
FigureTag FD4-709-05
+
-
+
-
BACKUP 2
PRIMARY 1
LISTED
SIMPLEX
FIRE ALARM
CONTROL
PANEL
2120,
4001, 4002
4020, 4100+, 4100U,
4100ES, 4004, 4005 OR
4006
BLK
SEE NOTE 4
SEE NOTE 4
SEE
NOTE
3
SEE NOTE 3
EOL
RESISTOR
(IF USED)
BLU
GRY
YEL
ORN
GRN
N/C
C
N/O
N/C
C
N/O
BLK
RED
VIO
(SEE NOTE 5)
(SEE NOTE 2)
BLK RED
REMOTE LED
4098-9830
(SEE NOTE 1)
2
1
3
4
INITIATING
CIRCUIT
Figure 2-4. 4098-9683 2-Wire Relay Base Connections for Style B or D Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized; refer to Figure 2-6 to wire remote LED to a heat
detector, observe color-coded wiring.
2. Wire only one relay base per initiating circuit.
3. For Style D initiating circuit, wire per dotted lines and do not use EOL resistor. If Style B
initiating circuit, refer to wiring diagrams provided with the system panel for proper EOL
resistor value.
4. It is recommended that the Primary-1 and the Backup-2 lines be in separate wire runs and in
compliance with local requirements.
5. Aux. Relay contacts, each rated 1 amp at 28 VDC/0.5 amp at 125 VAC, resistive.
Continued on next page
4098 Bases,
Continued
Wiring
2-13
FigureTag FD4-709-06
+
-
LISTED
SIMPLEX
FIRE ALARM
CONTROL
PANEL
2120,
4001, 4002
4020, 4100+, 4100U
4004, 4005 OR 4006
RED RED
BLK
BLK
RED
ORG ORG
BLK BLK
N/C
N/O
VIO
BLU
GRY
GRN GRN
SEE
NOTE
6
SEE
NOTE
6
ORG ORG
BLK BLK
N/C
N/O
VIO
BLU
GRY
GRN GRN
RELAY RELAY
ORG ORG
BLK BLK
N/C
N/O
VIO
BLU
GRY
GRN GRN
RELAY
INITIATING
CIRCUIT
RED RED
BLK
YEL
YEL
RED
24VDC
EOL RELAY
2098-9735
OR
2098-9739
RESETABLE
POWER
SOURCE
24VDC
REMOTE LED
4098-9830
(SEE NOTE 1)
EOL
RESISTOR
(SEE NOTE 3)
REMOTE LED
4098-9830
(SEE NOTE 1)
SEE
NOTE
6
+
-
4100ES
,
Figure 2-5. 4098-9682 4-Wire Base Connections for Style B Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized, observe color-coded wiring.
(Refer to Figure 2-6 to wire remote LED to heat detector.)
2. Aux. Alarm contacts - Form C - each rated 3 amps at 28 VDC/115 VAC, resistive.
3. Refer to wiring diagrams provided with system panel for proper EOL resistor value.
Continued on next page
4098 Bases,
Continued
Wiring
2-14
FigureTag FD4-709-07
+
-
+
-
BACKUP 2
PRIMARY 1
LISTED
SIMPLEX
FIRE ALARM
CONTROL
PANEL
2120,
2
1
3
4
SEE NOTE 2
SEE NOTE 2
SEE NOTE 3
SEE
NOTE
3
EOL
RESISTOR
(IF USED)
BLK
BLK
RED BROWN
WHITE
2
1
3
4
BLK
RED BROWN
WHITE
4098-9830
REMOTE LED
(SEE
NOTE 1)
4098-9684
HEAT DETECTOR
BASE
BLK
4098-9684
HEAT DETECTOR
BASE
INITIATING
CIRCUIT
4098-9830
REMOTE LED
(SEE
NOTE 1)
4001, 4002
4020, 4100+, 4100U
4004, 4005 OR 4006
4100ES
,
Figure 2-6. 4098-9684 Heat Detector LED Base Connections for Style B or D Initiating Circuits
Notes:
1. If used, 4098-9830 remote LED is polarized; observe color-coded wiring.
2. It is recommended that the Primary-1 and the Backup-2 lines be in separate wire runs and in
compliance with local requirements.
3. For Style D initiating circuit, wire per dotted lines and do not use EOL resistor. If Style B
initiating circuit, refer to wiring diagrams provided with the system panel for proper EOL
resistor value.
4098 Bases,
Continued
Wiring
3-1
This chapter contains general notes, specifications, and mounting information for the TrueAlarm
Sensors, Sensor Bases and QuickConnect Smoke Sensors.
WARNING: Be sure that the location of each smoke sensor and each heat
sensor has been planned per local and national fire codes
(see NFPA 72).
Smoke sensor sensitivities are set and continuously monitored by the control panel. This
functionality complies with NFPA 72. When functional testing of these sensors is required per
NFPA 72, use the test methods described in Chapter 5 of this manual “Compatibility and Testing.”
Refer to NFPA 72 for application, test, and maintenance requirements.
The 4098-9733 heat sensor and 4098-9754 multi-sensor provide a Rate-of-Rise function that is
software programmed and selectable at 15° F (8.3° C) or 20° F (11.1° C) per minute. The
4098-9733 and 4098-9754 also provide general temperature monitoring within the range of
32°-122° F (0°-50° C).
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
4098 TrueAlarm Sensors 3-2
4098 TrueAlarm Sensor Bases 3-3
4098 TrueAlarm QuickConnect Smoke Sensors 3-12
Table 3-1. 4098-9733 Spacing
Agency Program Selection Spacing
UL
135
º
F (57 C)
60 X 60 ft
(18.3 X 18.3 m)
UL
155
º
F (68 C)
40 X 40 ft
(12.2 X 12.2 m)
FM
135
º
F/155
º
F (57 C/68 C)
RTI = Quick
20 X 20 ft
(6.1 X 6.1 m)
FM
135
º
F/155
º
F (57 C/68 C)
with 15 or 20
º
F/min (8.3 or
11.1 C/min)Rate of Rise
RTI = Ultra Fast
50 X 50 ft
(15.2 X 15.2 m)
Chapter 3
TrueAlarm Sensors, Sensor Bases, and
QuickConnect Smoke Sensors
Introduction
In this Chapter
3-2
Table 3-2. TrueAlarm Sensor Specifications
Sensor PID
4098-9714 4098-
9717
4098-9733 4098-9754 4098-9746
Type of Sensor
Photoelectric Ionizat
ion
Heat Photo/Heat Gas
Average
Operating
Current
80 A 80 A
6 A at 68 F (20°C)
13 A at 135 F (57 C)
90 A
50µA
UL Temperature
Rating*
135 F (57 C)**
155 F (68 C)†
135 F (57 C)**
155 F (68 C)†
Humidity Range
(Non-Condensing)
10-95% RH
10-
95%
RH
10-95% RH 10-95% RH
15-95% RH
(15-90% for
long term
exposure)
Air Velocity
Range
0-2000 FPM
0-200
FPM
0-2000 FPM
0-1000 FPM
* Fixed temperature functions are software programmed and selectable from the UL temperature rating.
** UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 3600 sq. ft of Max. Coverage.
UL Max. Ambient Ceiling Temp. of 100° F (38° C) at 1600 sq. ft of Max. Coverage.
1. Smoke sensor sensitivities are set and continuously monitored by the control unit.
The sensitivity range (setting) for the 4098-9714 and 4098-9754 sensor is 0.2%/FT to
3.7%/FT smoke obscuration. The sensitivity range (setting) for 4098-9717 sensors is
0.5%/FT to 1.3%/FT.
2. The 0.2%/FT, 0.5%/FT, and 1.0%/FT settings for the 4098-9714 and 4098-9754 sensor and the
0.5%/FT and 0.9%/FT settings for the 4098-9717 sensor are for special applications only.
The 0.2%/FT, 0.5%/FT, 0.9%/FT, and 1.0%/FT settings are very sensitive settings: only use the
0.2%/FT setting when a sensor is located in a totally smoke-free and controlled
temperature environment, such as a computer room or telephone switching exchange.
3. To determine if an area is suitable for the 0.2%/FT setting, set the sensitivity for the installed
sensor at 1.5%/FT and monitor the peak values for 90 days. If you record a peak value of
0.1%FT or higher during the 90 days, do not use the 0.2%/FT setting.
4. To determine if an area is suitable for the 0.5%/FT setting, set the sensitivity for the installed
sensor at 1.5%/FT and monitor the peak values for 90 days. If you record a peak value of
0.25%FT or higher during the 90 days, do not use the 0.5%/FT setting.
5. To determine if an area is suitable for the 0.9%/FT or 1.0%/FT setting, set the sensitivity for
the installed sensor at 1.3%/FT (Ion) 1.5/FT (Photo) and monitor the peak values for
90 days. If you record a peak value of 0.5% or higher during the 90 days, do not use the
0.9%/FT (Ion) or 1.0%/FT (Photo) settings.
All sensors identified in Table 3-2 mount to a sensor base (refer to the “4098 TrueAlarm
Sensor Bases” section of this chapter for more information). Use the following information and
Figure 2-1 when mounting TrueAlarm sensors.
4098 TrueAlarm Sensors
Specifications
Special Applications
Mounting
3-3
TrueAlarm smoke/heat sensor bases are connected to a 2120 Multiplex Communicating Device
Transponder (CDT), 4020, 4100+, 4100U, 4100ES, 4120, 4008, or 4010 panel by a single wire
pair (MAPNET II/IDNet). The 4098-9792, -9789, 9793, 9796, 9797, and 9798 bases and their
sensors obtain both power and data over MAPNET II/IDNet wiring. The 4098-9791 sensor base
requires 24VDC power for relay operation and the 4098-9794 and 4098-9795 sensor base with
sounder requires 24 VDC or Notification Appliance Circuit (NAC) power. The 4098-9791, -9794,
-9795, and –9796 are NOT compatible with the 2120 CDT. The 4098-9793 is only compatible
with the 4010, 4008, 4100U and 4100ES (except with 4100-3103 Quad Panel Isolator).
The table below contains specifications for TrueAlarm Sensor Bases.
Table 3-3. TrueAlarm Sensor Bases Specifications
Sensor Base
PID
4098-9789
(w/
Remote
LED)
4098-9791
(w/ Relay
and
Remote
LED)
4098-9792
4098-9793
(Isolator
Base)
4098-9794
(Sounder
Base)
4098-9795
(Multi-
Sensor
Sounder
Base)
4098-9796
(Multi-
Sensor w/
Remote
LED)
4098-9797
(CO Sensor
Base)
4098-9798
(CO Sounder
Base)
Working
Voltage
(MAPNET
II/IDNet)
24-40 VDC
24-40
VDC
24-40
VDC
24-40 VDC 24-40 VDC 24-40 VDC 24-40 VDC 24-40 VDC 24-40 VDC
24V Working
Voltage
(Relay or
Sounder
Power)
18 – 32
VDC
18 – 32
VDC
18 – 32
VDC
18 – 32 VDC
MAPNET
II/IDNet
Current *
400 A 400 A 400 A 500 A 400 A 500 A 500 A 450 A 500 A
24V Standby
Current
(Relay or
Sounder)
270 A 270 A 270 A 270 A
24V Current
(Relay or
Sounder
Activated)
28 mA
17 mA 20 mA
17 mA
LED Output Yes Yes
Yes Yes Yes
Yes
Sounder
Output
88 dBA
minimum
88 dBA
minimum
88 dBA
minimum
* MAPNET II/IDNet current with Photo Sensor plugged into Base
Each sensor base has a unique address. This address is associated with a custom label that
identifies its physical location within a building. The base’s address and location must match up
with the address listed in the specification sheets of the 2120 Job Configuration Report or the
Programmer’s Report for the 4020, 4100+, 4100U, 4100ES, 4120, 4008, or 4010 System. See
Figure 3-1 for DIP Switch location for 4098-9789, -9791, -9792, -9793, and -9796, Sensor Bases.
See Figure 3-2 for DIP Switch location for 4098-9794, 4098-9795, -9797 and -9798.
Continued on next page
4098 TrueAlarm Sensor Bases
Introduction
Specifications
Setting the Base’s
Address
3-4
12345678
128
64
32
16
8
4
2
1
ON OFF
Figure 3-1. 4098-9789, -9791, -9792, -9793, -9796, Sensor Bases Location of DIP Switches
Figure 3-2. 4098-9794, 4098-9795, , 4098-9798 Sensor Bases Location of DIP Switches
Note: The 4098-9794 Sounder Base, 4098-9795 Multi-Sensor Sounder Base, and 4098-9798
Sounder Base have a 9-position DIP Switch. The first eight DIP Switches set the sounder
base address. DIP Switch Position 9 is set to OFF or ON depending upon the sounder base
power source. When the sounder base is connected to a 24 VDC power source, DIP
Switch Position 9 is set to “OFF” and the 24 VDC power is supervised by the sounder
base. When the sounder base is powered by the panel’s Notification Appliance Circuit
(NAC), DIP Switch Position 9 is set to “ON” and the power is supervised by the NAC and
not the sounder base. The -9797 Base has the same layout, but doesn’t offer sounder
functionality. It uses only an 8-way DIP switch.
Continued on next page
4098 TrueAlarm Sensor Bases,
Continued
Setting the Base’s
Address
DIP Switch Position 9
“ON” for NAC Power Input
DIP Switch Position 9
“OFF” for 24 VDC
Power Input
“ON” Position
DIP Switches
“OFF” Position
DIP Switches
3-5
1. Using the 2120 Job Configuration Report, find the entry for the sensor base (4098-9792 and
4098-9789 only) you are about to install. The CUSTOM LABEL column provides the
location while the DEVICE ADDRESS column provides the switch setting data.
2. Using the switch setting data for the base you are installing, set the base’s address.
See Figure 3-1 for location of switches. Use a small screwdriver or pen to set the switches.
3. Double-check the location of the sensor base and its address before proceeding to electrical
installation (see Figure 2-1).
1. Using the Programmer’s Report for the 4020 (Figure 3-3), 4100+, 4100U, 4100ES, 4120,
4008, or 4010 (Figure 3-4), find the entry for the sensor base you are about to install. The
device ADDRESS and CUSTOM LABEL are located in the SYSTEM POINT SUMMARY
under “M.”For example, Address M1-7 (for the 4100+, 4100U, 4100ES, 4120, 4008, or 4010
system) is circled in Figure 3-4. M1 is the addressable channel while -7 is the device address
on the channel. For a base with Address M1-7, Address 7 must be set on the base’s DIP
Switches (SW1).
2. Using the example given in Step 1 as guideline, set the base’s address using the information in
Figure 3-5. See Figure 3-1 and 3-2 for location of DIP Switches. Use a small screwdriver or
pen to set the switches.
3. Mark an address label with the appropriate address for your base by shading a label box for
each base DIP Switch in the ON position. Then apply the label to the base near the base’s
DIP Switch.
4. Double-check the location of the sensor base and its address before proceeding to electrical
installation.
Figure 3-3. 4020 Programmer’s Report
Figure 3-4. 4100+, 4100U, 4100ES, 4120, 4008, or 4010 Programmer’s Report
Continued on next page
4098 TrueAlarm Sensor Bases,
Continued
Address Setting for
the 2120 CDT
System
Address Setting for
the 4010, 4020,
4100+, 4100U,
4100ES, 4008, or
4120 System
Device
Address
Device
Address
3-6
The figure below shows the address DIP Switch settings for the 4010, 4008, 4020, 4100+, 4100U,
4100ES and 4120 Systems. Refer to the “Compatibility and Testing” chapter of this publication
for information on which devices are compatible with the various FACPs.
Note: The 4020, 4100+, 4100U, 4100ES, 4008, and 4120 systems support up to 127 devices on
each of their MAPNET II channels. The 4010 supports up to 250 devices on its IDNet
channel.
FigureTag FD4-709-08
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000
0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240
1000
1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241
0100
2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
1100
3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243
0010
4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
1010
5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245
0110
6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
1110
7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247
0001
8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
1001
9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249
0101
10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
1101
11 27 43 59 75 91 107 123 139 155 171 187 203 219 235
0011
12 28 44 60 76 92 108 124 140 156 172 188 204 220 236
1011
13 29 45 61 77 93 109 125 141 157 173 189 205 221 237
0111
14 30 46 62 78 94 110 126 142 158 174 190 206 222 238
15 31 47 63 79 95 111 127 143 159 175 191 207 223 239
LSB
MSB
1 2345678
1111
DIP SWITCHES 5 THRU 8
ON
OFF
1 = ON 0 = OFF
251
252
253
254
255
DIPSWITCH IS SHOWN SET AT ADDRESS 7.
Figure 3-5. 4010, 4020, 4100+, 4100U, 4100ES, 4008, or 4120 MAPNET/IDNet Addresses
Continued on next page
4098 TrueAlarm Sensor Bases,
Continued
Address Setting for
the 4010, 4020,
4100+, 4100U,
4100ES, 4008, or
4120 System
3-7
The 4098-9795 and 4098-9796 Multi-Sensor Bases are only
for use with the 4098-9754
multi-sensor and are not compatible with the 2120 CDT. Both bases have remote LED output and
the 4098-9795 also has an integrated sounder similar to the 4098-9794 Sounder Base. The
4098-9795 and 4098-9796 Multi-Sensor Bases must be used with the 4098-9754 multi-sensor
when connected to a 4010, 4020, 4100+, 4008, or 4120 system. When connected to a 4100U or a
4100ES the 4098-9754 multi-sensor can also be used with the 4098-9789, -9791, -9792, -9793, -
9794, -9797, and -9798 bases.
The Multi-Sensor Base answers to two addresses, therefore the DIP Switch must be set for
even addresses only
. The even address is a photo sensor/sounder base (4098-9795) or a photo
sensor/standard base (4098-9796), and the odd address (DIP Switch + 1) is a heat sensor/standard
base. The figure below shows the allowable addresses for the Multi-Sensor Bases.
IMPORTANT: Switch Position 1 is not used and must always be OFF (0) for the
Multi-Sensor Bases to function properly. The odd address immediately
after the DIP Switch setting must not be used by any other sensor base or
MAPNET/IDNet device.
0000 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111
0000
0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240
0100
2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242
0010
4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244
0110
6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246
0001
8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248
0101
10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250
0011
12 28 44 60 76 92 108 124 140 156 172 188 204 220 236
0111
14 30 46 62 78 94 110 126 142 158 174 190 206 222 238
LSB MSB
1 23456789
DIP SWITCHES 5 THRU 8
SWITCH 1 MUST BE SET TO OFF
FOR PROPER OPERATION
RESERVED FOR FUTURE USE
RESERVED FOR
FUTURE USE
DIP
SWITCHES
1 THRU 4
ON
OFF
1 = ON 0 = OFF
252
254
DIPSWITCH IS SHOWN
SET AT ADDRESS 4.
SEE
NOTE 1
SEE
NOTE
Figure 3-6. 4098-9795, -9796, 9798 Multi-Sensor Base DIP Switch Address Settings
Note: The 4098-9795 Multi-Sensor Sounder Base has a 9-position DIP Switch that is used for
setting base address and selecting the sounder power source. See Figure 3-2 for DIP Switch
location.
Sensor bases are connected to the fire alarm control panel via a single wire pair for the 4098-9789,
-9792, -9793, -9796, and -9797 and two pairs of wires for the 4098-9791, -9794, -9795, and -9798.
Using Figure 3-7 as a reference, connect the bases to the MAPNET II/IDNet wire pair and 24V
power
(if used).
IMPORTANT: For additions to existing installations, remove power from the panel
before wiring any bases to avoid damage to equipment.
Continued on next page
4098 TrueAlarm Sensor Bases,
Continued
Multi-Sensor Bases
4098-9795 and
4098-9796
Wiring
3-8
FigureTag FD4-709-09
2979-8904
-COMM
+COMM
-COMM
+COMM
-COMM
+COMM
-COMM
+COMM
6979-,9879-8904
BLUE
WHITE
WHITE
BLUE
1979-8904
+
-
BLUE
WHITE
teNDI/IITENPAM+
teNDI/IITENPAM-
BLACK/WHITE
BLACK
V42+
V0
V42+
V0
MORF
LENAP
SECIVEDV42REHTOOT
REHTOOT
/IITENPAM
SECIVEDteNDI
)2ETONEES(
ESABROSNESESABROSNES ESABROSNES
.O.N
R
E
TNEC
.C.N
NEERG
E
G
NARO
7379-8902
YALER
EES(
)9ETON
KCALB
KCALB
EUL
B
TELOIV
YERG
WOLLEY
RETNEC
.C.N
.O.N
2289-8904
YALER
ELUDOM
EULB
ETIHW
DER
DER
KCALB
KCALB
NWORB
T
EL
O
I
V
YERG
.O.N
RETNEC
.C.N
BTCATNOC
)4ETONEES(
EGNARO
W
OLLEY
NEERG
RETNEC
.C.N
.O.N
ATCATNOC
)4ETONEES(
EES(
)5ETON
EES(
)6ETON
EES(
)9ETON
+
-
80
89
-
89
02
DELETOMER
2289-8904RO
)DESUFI(YALER
)1ETONEES(
+
-
TXENOT
CANROV42
TIUCRIC
+24V OR NAC +ALM
0V OR NAC -ALM
MORF
LENAP
BTCATNOC
)7ETONEES(
ATCATNOC
)7ETONEES(
3979-8904
ESABROSNES
)8ETONES(
REHTOOT
S
ECIVEDTENDI
)2ETONEES(
EES(
)6ETON
5979-,4979-8904
+S
+
-
-S
MORF
LENAP
teNDI/IITENPAM+
teNDI/IITENPAM-
DLEIHS
)3ETONEES(
DLEIHS
)3ETONEES(
DLEIHS
)3ETONEES(
DLEIHS
)3ETONEES(
-9797 , -979 8
)01&8SETONEES(
MORF
0104
LENAP
L
A
NO
I
TPOSI
D
L
E
IHS
)3ETONEES(
DLEIHS
COMM
COMM
COMM
COMM
teNDI
teNDI
-73erugiF moke/Heat Sensor Base ConnectionsS
Notes:
1. Remote LED and relay wires are not supervised.
2. Maximum quantity of devices per circuit is 127 for 4020, 4100+, 4100U/4100ES (MAPNET), or 4120, 128 for the 2120 CDT panel, 200 for the 4008 panel, and 250 for the 4010 and
4100U/4100ES (IDNET) panel. Maximum quantity of 4098-9795 -9796 and -9797 Multi-Sensor bases is 63 with 4020, 4100+, 4100U,
4100ES and 4120, 100 for 4008 panel, and 124
for the 4010 panel. If the sounder output is coded (Temporal code, etc.) via MAPNET II/IDNet control see Note 10.
3. If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated from electrical box.
4. Contact A or B: Dry, Form C - each rated 2 amperes at 24 VDC/0.5 amperes at 110 VAC, resistive.
5. 18 to 32 VDC, .008 amperes typical/.013 amperes max.
6. Do not use remote LED if the 4098-9822 relay module is used.
7. Contact A or B: Dry, Form C – Each rated at 3 amperes at 28 VDC/115 VAC, resistive.
8. Remove the protective tape over the CO Sensor on the 4098-9797 and -9798 bases only after the sensor head has been installed.
9. Maximum wire length between 4098-9791 sensor base and 2098-9737 relay module is 100 feet.
10. Maximum quantity of sensors with 4098-9794, -9795, and -9798 sounder bases limited to 43 if output is coded (Temporal code, etc.) via MAPNET II/IDNet control.
If coding is performed via 24VDC or NAC circuit, see Note 2.
Continued on next page
4098 TrueAlarm Sensor Bases,
Continued
Wiring
3-9
Figure 3-8 shows the wiring connections for the isolator sensor base. All screw terminals accept
14 to 18-gauge AWG solid or stranded. Maximum torque should not exceed 12-inch-pounds.
CAUTION: Do not loop wire under terminals. Break wire runs to provide
supervision.
Figure 3-8. 4098-9793 Isolator Sensor Base Connections
Notes:
1. Isolator base compatible with 4010, 4100U, 4100ES or 4008 panel ONLY.
2. Maximum quantity of devices per circuit is 250 for 4010, 4100U and 4100ES panels.
3. If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated
from electrical box.
4098 TrueAlarm Sensor Bases,
Continued
Wiring
3-10
This section contains the instructions for the end-of-life replacement of the 4098-9746 CO
Replacement Cartridge (CORC), in the CO SSD Bases (Carbon Monoxide Smoke Sensor and
Detector Bases). Replacement is necessary due to normal component degradation over time. It is
standard maintenance for the CO SSD Bases in order to prolong normal function without requiring
base replacement.
Note: During installation, you may be exposed to live circuits - attention required to ensure
personal safety and to avoid product damage.
Model number reference:
Model Name
4098-9746 CORC Replacement
4098-9797 CO SSD Sensor Base
4098-9798 CO SSD Sounder Base
Removing the expired CORC
1. Remove sensor head (not shown) and set aside for later re-installation.
2. Insert a fine blade screwdriver into the slot, as shown below.
3. Gently free the CORC from the sensor base by pushing straight in. Do not pry. Remove the
CORC and dispose.
Figure 3-9. Removing the CORC from the Sensor Base
______________________________________________________________________________
Continued on next page
4098 TrueAlarm Sensor Bases,
Continued
CRS Replacement
Instructions
3-11
Installing the replacement CORC (refer to photo below)
1. Remove the replacement CORC from its packaging.
2. Hook the loop of the CORC on the tab in the outer rim of the base (center of the CORC below
the CO sensor cylinder)
3. Gently rotate the CORC inward until it snaps onto the CO SSD Sensor Base.
4. Re-install the detector head.
5. Remove the dust cover from the CORC (shown to the side below).
6. The CORC replacement is complete.
Figure 3-10. Installing the replacement CORC
4098 TrueAlarm Sensor Bases,
Continued
CRS Replacement
Instructions
3-12
This section contains general notes, specifications, and mounting information for the TrueAlarm
QuickConnect Smoke Sensor shown in Table 3-4.
WARNING: Ensure that the location of each smoke sensor has been planned
per local and national fire codes (see NFPA 72).
1. Smoke sensor sensitivities are set and continuously monitored by the control panel.
This functionality complies with NFPA 72. When functional testing of these sensors is
required per NFPA 72, use the test methods described in the “Compatibility and Testing”
chapter of this publication. The sensitivity range (settings) of the 4098-9757 is 1.5%/ft to
3.7%/ft smoke obscuration.
2. Refer to NFPA 72 for application, test, and maintenance requirements.
Table 3-4. TrueAlarm QuickConnect Smoke Sensor Specifications
Sensor PID 4098-9757
Type of Sensor
Photoelectric
Operating Current
500 A max.
Humidity Range (Non-Condensing)
10-95% RH
Air Velocity Range
0-2000 FPM
Working Voltage
(MAPNET II and IDNet)
24-40 VDC
24V Working Voltage
(Sounder Power
Sounder Output
24V Standby Current
(Sounder)
24V Current
(Sounder Activated)
Remote LED Output
NO
Continued on next page
4098 TrueAlarm QuickConnect Smoke Sensors
Overview
Specifications
3-13
The 4098-9757 QuickConnect2 sensor requires the 4098-9788 base.
The 4098-9757 QuickConnect2 sensor is only compatible with the 4010, 4100U and 4100ES (with
4100-3106). The sensors obtain both power and data over IDNet wiring.
Each QuickConnect sensor has a unique address. This address is associated with a custom label
that identifies its physical location within a building. The sensor’s address and location must
match up with the address listed in the Programmer’s Report for the 4010, 4100U or the 4100ES.
Use the method described in the “4098 TrueAlarm Sensor Bases” section of this chapter to
complete the sensor setup. Refer to the figure below for the location of the DIP Switches.
Double-check the location of the QuickConnect sensor and its address before proceeding to
electrical installation (see Figures 3-12 and 3-13).
Figure 3-11. Location of DIP Switches on QuickConnect Sensor
Continued on next page
4098 TrueAlarm QuickConnect Smoke Sensors,
Continued
Specifications
Setting the
Sensor’s Address
Address DIP Switches
4098-9757
3-14
Use the following to wire the QuickConnect smoke sensors.
CAUTION: Do not loop wire under terminals. Break wire runs to provide
supervision.
(SEE
NOTE 1)
4098-9788
FROM
PANEL
-IDNet
+IDNet
SHIELD IS
OPTIONAL
(SEE NOTE 3)
SHIELD
SHIELD
SHIELD
TO OTHER IDNet
DEVICES
(SEE NOTE 2)
-IDNet
+IDNet
4098-9788
4098-9788
Figure 3-12. QuickConnect Sensor Connections
FigureTag FD4-709-10
Notes:
1. 4098-9757 QuickConnect sensor uses the 4098-9788 base.
2. Maximum quantity of devices per IDNet circuit is 250 for the 4010, 4100U and 4100ES (with
4190-3106) panel.
3. If shield is used, twist shield wires together and cap with wire nut. Shield should be insulated
from electrical box.
4098 TrueAlarm QuickConnect Smoke Sensors,
Continued
Wiring
4-1
This chapter covers relay module accessories.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Relay Module Accessories 4-2
Chapter 4
Accessories
Introduction
In this Chapter
4-2
The 2098-9737 Relay module is used with 4098-9791 sensor base. Install the relay module using
Figure 3-7 and the figure below as a reference.
Figure 4-1. 2098-9737 Relay Module Wiring
Notes:
1. 18 to 32 VDC 24 mA typical/35 mA maximum.
2. Contact A or B: dry, Form C, each rated 3 amps at 28 VDC/115 VAC, resistive.
3. Maximum wire length between sensor and relay module is 100 feet.
Continued on next page
Relay Module Accessories
2098-9737
Relay Module Wiring
4-3
The 4098-9822 Relay Module is used with the 4098-9789, -9791, -9794, -9795, and -9796
Sensor Bases. Install the relay module using Figure 3-7 and the figure below as a reference.
IMPORTANT: Do not use a remote LED if using the 4098-9822 relay module.
The 4098-9822 relay module is not supervised and should only be
used for non-critical supplementary functions. There is a limit of
ten control outputs activated on a MAPNET II/IDNet channel. If the
channel capacity is exceeded, the relay module may not function
properly.
FigureTag FD4-709-10
FROM
PANEL
(IF USED)
+24VDC
4098-9822
RELAY
BLUE
WHITE
+WHITE
VIOLET
BROWN
GREY
YELLOW
ORANGE
GREEN
N.C.
CENTER
N.O.
N.C.
CENTER
N.O.
CONTACT A
(SEE NOTE 3)
TO OTHER 24VDC
DEVICES OR
SUPERVISORY MODULE
CONTACT B
(SEE NOTE 3)
RED
RED
BLACK
BLACK
-BLUE
+24VDC
0V0V
(SEE NOTE 1)
(SEE NOTE 2)
Figure 4-2. 4098-9822 Relay Module Wiring
Notes:
1. Do not use remote LED.
2. 18 to 32 VDC, .008 amps typical / .013 amps. Maximum.
3. Contact A or B: Dry, Form “C” - each rated 2 amps resistive at 24 VDC/0.5 amps at
110 VAC, resistive.
Continued on next page
Relay Module Accessories,
Continued
4098-9822 Relay
Module Wiring
From 4098-9789, -9791, -9794,-9795, -9796
Sensor Base
4-4
Install the relay module using the following steps:
1. Mount a 1-1/2 inch (3.81 cm) extension ring (not supplied) to an octagonal or square
electrical box (not supplied). The extension ring is required to meet the minimum box
volume requirement (32.3 cu. inch/529.4 cu. cm) for relay module installation.
2. Mount relay module inside extension ring directly behind base and sensor. Do not mount
remotely. See Figure 4-1 or 4-2 for relay module connections.
Note: Use the exact configuration of electrical box (square or octagonal) with extension to
mount sensor base when installing the relay module.
The 2098-9808 Remote LED Module is available for the 4098-9789 ,-9791, -9794, -9795, -9796
Sensor Bases.
Use the figure below as a reference when installing the Remote LED Module to a sensor base.
RED BLACK
LED
2098-9808
Figure 4-3. 2098-9808 Remote LED Module Wiring
Relay Module Accessories,
Continued
Relay Module
Installation
Remote LED Module
To 4098-9789, -9791, -9794, -9795, -9796 Sensor Base
5-1
This chapter covers the compatibility of 4098 Sensors, Detectors, and Bases. Maintenance and
testing are also covered.
Refer to the page number listed in this table for information on a specific topic.
Topic See Page #
Compatibility 5-2
Maintenance and Testing 5-4
Cleaning 5-8
Trouble Indications 5-9
Fire Alarm Trouble and Maintenance Log 5-11
Chapter 5
Compatibility and Testing
Introduction
In this Chapter
5-2
This section describes the compatibility between FACPs, detectors, and detector bases.
Table 5-1. 4098 Detector and Detector Base Compatibility
Detectors
Compatible 2-
Wire Detector
Base
System
Max. Quantity
of Bases per
Initiating
Circuit
4098-9601 4098-9788 2120 ET/FADM 25
4098-9602 4098-9684 2120 FABT/VPBT 18
4098-9603 (LED base for 2120/4100+ ZAM 20
4098-9605 Heat Detectors 4001 18
4098-9612 Only) 4002 30
4098-9613
4020 30
4098-9614
4100ES/4100U/4100+/4120/UT 30
4098-9615
4004/4005 20
4006 30
4004/4005 High Current 30
4098-9683
(Relay base not used with
4004 and 4005 Low Current
systems)
1
(See Note 1)
Notes:
1. Relay operation cannot be guaranteed unless it is the only device on that zone.
2. Panel compatibility identification marker is model number of the module or panel.
3. Detector compatibility identification marker is model number found on detector label.
4. For detailed interconnection data, see wiring diagrams for specific panels.
5. For additional compatibility listings see 579-832 for 2-wire detector compatibility charts.
Continued on next page
Compatibility
Compatibility for
4098 Detectors and
Detector Bases
5-3
This section describes the compatibility between FACPs, sensors, and sensor bases.
Table 5-2. 4098 Sensor and Sensor Base Compatibility
Sensors Compatible Bases Max. Quantity of Devices Per Circuit
4098-9714
4098-9717
4098-9733
4098-9789
4098-9791
4098-9792
MAPNET II:
127 (4020), 127 (4100+)
127 (4120), 127 (4100U), 127 (4100ES)
Addresses 1-127
4098-9714
4098-9717
4098-9733
4098-9789
4098-9792
128 (CDT TrueAlarm)
Addresses 0-127
4098-9714
4098-9717
4098-9733
4098-9789
4098-9791
4098-9792
4098-9793
4098-9797 (4100U/4100ES
only)
IDNET:
250 (4010), 250 (4100U), 250 (4100ES)
Addresses 1-250
4098-9714
4098-9733
4098-9789
4098-9791
4098-9792
4098-9793
IDNET:
200 (4008)
Addresses 1-200
4098-9714
4098-9717
4098-9733
4098-9794
(See Note 5)
4098-9798
(See Note 5)
(4100U/4100ES, IDNet only)
MAPNET II:
127 (4020), 127 (4100+)
127 (4100U), 127 (4100ES), 127 (4120)
Addresses 1-127
IDNET:
250 (4010), 250(4100U), 250 (4100ES)
Addresses 1-250
4098-9754
4098-9795
(See Note 5)
4098-9796
MAPNET II:
63 (4020, 4100+, 4100U, 4100ES, 4120)
Addresses 2 to 126
IDNET:
124 (4010), 124 (4100U), 124 (4100ES)
Addresses 2 to 248
4098-9754
4098-9792
4098-9789
4098-9791
4098-9794
(See Note 5)
4098-9797
4098-9798
(See Note 5)
IDNET:
250 (4100U), 250 (4100ES)
Addresses 1-250
4098-9757
4098-9788
IDNET:
250 (4100U/4100ES with 4100-3106)
250 (4010)
Addresses 1-250
4098-9746
4098-9797
4098-9798
(See Note 5)
IDNET:
250 (4100U), 250 (4100ES)
Addresses 1-250
Compatibility, Continued
Compatibility for
4098 Detectors and
Detector Bases
Notes:
1. For detailed interconnection data,
see wiring diagrams for specific
panels.
2. Panel compatibility identification
marker is model number of the
module or panel.
3. Sensor compatibility identification
marker is model number found
on sensor label.
4. 4098-9754 sensor NOT compatible
with bases that have a RED DOT
located in sensor mounting area.
5. Maximum quantity of 4098-9794
Sounder Bases, 4098-9795
Multi-Sensor Sounder Bases, and CO
Sounder bases (4098-9798) when
output is coded via MAPNET II/IDNet
control (Temporal Code) is 43.
If coding is performed via 24 VDC or
NAC circuit, use limits specified in
Table 5-2.
5-4
The minimal requirement for detector and sensor maintenance should consist of clearing surface
dust by using a vacuum cleaner. Cleaning programs should comply with NFPA and local
environments. Cleaning of the internal chamber should only be done by a qualified technical
representative.
For service, return to your local branch office.
Smoke sensor sensitivities are set and continuously monitored by the control unit. Dirty or
out-or-range sensors are annunciated by the control unit. This functionality complies with
NFPA 72.
Note: When testing detectors/sensors, refer to NFPA 72, or contact your local branch office.
CAUTION: Before functionally testing the detectors/sensors, be sure to disconnect
the city connection, releasing devices, and extinguishing systems
(or for the 4020, 4010, 4100+, 4100U, 4100ES, 4006, 4008, or 4120 panel,
put the panel in the Walk Test mode).
NFPA minimally requires annual functional testing of smoke detectors/sensors at their installed
location. To perform this annual test, use the Solo 336 Aerosol Smoke Dispenser.
IMPORTANT: After testing detectors, reset the fire alarm panel to restore the fire
alarm system to normal status. After testing sensors, you must
clear the peak values.
The following test equipment is available:
553-760: Test and Removal Tool – attached to Mr. Longarm 4 ft. pole (Item #7508) or
6 ft. pole (Item #7512).
553-761: Heat Detector/Sensor Removal Adapter (use with 553-760).
553-635: Aerosol spray, Simplex Dry Smoke.
553-805: Removal Adapter Head Attachment (attaches to the 553-760 tool).
553-810: Magnet Tester – attached to Mr. Longarm 4 ft. pole (Item #7508) or 6 ft. pole
(Item #7512).
553-832: Ion Detector Test Cable.
Also available are the:
Gemini Sensitivity Tester (Model 501 or 502).
Solo 336 Aerosol Smoke Dispenser –attached to either the Solo 100 (15 ft.)
telescopic fiberglass pole or the Solo 101 (4 ft.) fiberglass pole.
Solo A4 Aerosol Spray.
Solo Red Cup (709-024). Use to hold the 553-635 Aerosol Spray Can.
Solo (708-021) Adapter for Solo Poles. Use to adapt 553-760 Test and Removal
Tool to the Solo Pole.
TrueTest 801 – Smoke Detector Sensitivity Test Equipment.
Smoke 400 – Smoke aerosol for TrueTest.
Note: The TrueTest 801 is the only tester to be used with the 4098-9797 and 4098-9798 bases.
Continued on next page
Maintenance and Testing
Maintenance
Preferred Method of
Testing Smoke
Detectors/Sensors
Test Equipment
Available
Testing
5-5
The following test method is suitable for functional checks of sensor bases or QuickConnect
sensors during installation; however, testing with smoke must be performed to comply with NFPA
requirements.
For all sensor bases, position the 553-810 Magnet Tester ½” to ¾” counterclockwise from the
visible LED found on the sensor base, (see the figure below).
For the 4098-9757 QuickConnect2 photo sensor, position the 553-810 Magnet Tester as shown in
Figure 5-2.
Testing a sensor with a magnet reports a value of 255 for actual / peak (exception 4010 panel,
4100U panel and 4100ES panel). Clear the peak value after testing.
Note: For 4098-9795 and 4098-9796 Multi-Sensor Bases both photo and heat address
(even and odd) must alarm.
Figure 5-1. Magnet Test Location for 4098-9789, -9791, -9792, -9793, and -9796
Sensor Bases using 553-810 Magnet Tester
The 4098 photoelectric detectors may be tested by placing a magnet above the location indicated
by a “ mark embossed on the cover (see Figure 5-2) for four (4) seconds. Use the Magnetic
Tester (Part No. 553-810), Table 5-3, and the following information to test detectors.
Table 5-3 describes the LED reaction during Normal and MAG TEST modes to the Normal,
More Sensitive, Less Sensitive, and Non-Functional states of the detector.
Continued on next page
Maintenance and Testing,
Continued
Alternate Method for
Testing Sensors
Magnetic Test for
Photoelectric
Detectors
5-6
Figure 5-2. Magnet Test Location for 4098-9601, -9602, -9603, -9605
Smoke Detectors using 553-810 Magnet Tester
Table 5-3. MAG TEST/Normal Modes - States and Reactions
STATE Normal Mode MAG TEST Mode
(LED flashes
every 4 secs.)
LED Flashes
Quickly 6
Times
LED Flashes
Slowly 4 Times
Latches in Alarm
Mode/LED stays “ON”
Normal
X X
More Sensitive
X X X
Less Sensitive
X X X
Non-Functional
X
When placing the magnet at the location indicated by a “ mark embossed on the cover, the
visible LED flashes indicating the detector's condition. The following are descriptions of what
you should see when using the MAG TEST.
NORMAL - When in MAG TEST, the detector latches into alarm if the detector is within
calibration range and the visible LED stays ON.
MORE SENSITIVE - When in MAG TEST, if the detector is more sensitive than the
maximum calibration, the visible LED quickly flashes, twice a second. Following the sixth
flash, the detector latches into alarm and the visible LED stays ON.
LESS SENSITIVE - When in MAG TEST, if the detector is less sensitive than the minimum
calibration, the visible LED slowly flashes four times, once every two seconds. Following the
fourth flash, the detector latches into alarm and the visible LED stays ON.
NON-FUNCTIONAL DETECTOR - If the detector is less sensitive than the minimum
allowable sensitivity or if there is a fault in the temperature sensing circuit (4098-9602), the
visible LED does not flash normally. When in MAG TEST, the visible LED slowly flashes
four times, once every two seconds. After the fourth flash, the detector does NOT latch into
alarm and the LED stops flashing and turns OFF.
If the detector is out of the normal operating range, it should be cleaned. If the detector still
indicates as other than normal sensitivity, replace the detector.
Continued on next page
Maintenance and Testing,
Continued
Magnetic Test for
Photoelectric
Detectors
5-7
The 4098 Ionization Detectors may be tested with a magnet to verify proper operation of the
Fire Alarm Control Panel.
Note: When ionization detectors alarm, the red LED indicator activates and latches into the
ON position.
Place a magnet against the detector’s side (over the location marked by a” on the head of the
ionization detector) and hold for ten seconds to activate an internal reed switch. Use the Magnet
Tester (Part No. 553-810).
Plug the 553-832 Ion Detector Test Cable into the Detector’s sensitivity voltage pins located on
the Ion Detector Head. Perform the following steps to test the Ion detector’s sensitivity:
1. Connect a 10M/V digital voltmeter to the 553-832 test cable, connect the negative terminal of
the voltmeter to the red wire of the test cable and connect the positive terminal of the
voltmeter to the white wire of the test cable. The black wire of the 553-832 test cable is not
used.
2. The voltage measured by the voltmeter should be within 0.2 and 0.8 volts. Detectors
outputting a voltage outside this range should be cleaned or replaced.
3. If the Ion Detector voltage output is outside of the range, it should be removed and cleaned as
described in the cleaning section. Re-check the voltage measurement on the Ion Detector; if
the Ion Detector is still outside the voltage range after cleaning, replace the device.
Maintenance and Testing,
Continued
Magnetic Test for
Ionization Detectors
Ion Detector
Sensitivity Test
5-8
If the device’s sensitivity is other than what is marked on the device’s label, clean the device using
a source of oil-free, filtered, compressed air such as Dust-Off, Tech Duster, etc.
CAUTION: Notify appropriate building personnel prior to removing any
detectors/sensors from service.
Blow the compressed air through the open vents around the device so that air enters and cleans the
black chamber cover/insect screen assembly (Part No. 677-224) located beneath the white
protective cover.
If the device’s sensitivity is still other than what is marked on the device’s label, replace the
device.
Note:
Do not remove the Ion Detector/ Sensor protective cover.
Blow compressed air through the open vents around the device so that air enters and cleans the
black chamber cover assembly located beneath the white protective cover. If the device sensitivity
is still outside the marked range replace the device and return the failed device to 130 Perinton
Parkway, Fairport, NY 14450-9199.
IMPORTANT: Once cleaned, the detector/sensor should be tested with smoke per
NFPA 72.
Cleaning
Introduction
Photoelectric Smoke
Detector/Sensor
Cleaning
Special
Considerations for
Ion Detectors and
Sensors
5-9
The TrueAlarm smoke sensor is a measuring device that sends data regarding smoke density to the
4010, 4020, 4100, 4100+, 4100U, 4100ES, 4008, and 2120 fire alarm control panels (FACPs).
The TrueAlarm heat sensor operates in a similar fashion, but sends temperature data instead of
smoke density data. The FACP uses this data to determine whether a trouble has occurred.
The TrueAlarm sensor has two automatic trouble indications:
Dirty
Excessively Dirty
A “Smoke Sensor Dirty” trouble condition is reported any time the average value on an individual
sensor reaches a set threshold value. At this time, the FACP is still compensating for environmental
factors and is holding the set sensitivity level.
A “Smoke Sensor is Excessively Dirty” trouble condition is reported anytime the average value of
an individual sensor reaches a slightly higher set threshold level. At this point, the FACP can no
longer compensate for environmental factors, and the sensitivity level may begin to drift.
Although an “excessively dirty” trouble is reported, the sensor continues to operate and reports an
alarm condition when one is detected.
In addition to the two automatic trouble conditions, the FACPs have digital pseudo points that
must be turned ON to allow a TrueAlarm sensor that is close to being a dirty sensor to report as if
it is “almost dirty.” This is useful when maintenance is being scheduled for dirty sensors, as it
provides a means of seeing if other sensors are approaching a dirty state.
The table below shows your responsibilities when certain trouble indications occur.
Table 5-4. TrueAlarm Troubles and Descriptions
Trouble Indication Description
Almost Dirty
Using the front panel keys, it is possible for a technical representative to turn
ON a digital pseudo point in the FACP that allows an “almost dirty” sensor to
report a trouble. Although the “almost dirty” sensor is holding its sensitivity
level, you can schedule maintenance for the sensor before the dirty sensor
trouble occurs.
Dirty
A “dirty” indication means that the sensor is holding its sensitivity level, but that
you should schedule maintenance for the sensor. Clean the sensor as required
and, when necessary, call your local branch office for service.
Excessively Dirty
The “excessively dirty” indication means that the sensor is no longer
compensating for dirt and dust. Because nuisance alarms are possible with this
condition, sensors must be cleaned or replaced immediately. When necessary,
call your local branch office for service.
Self-Test Abnormal
All FACP system sensors are automatically tested once every minute. When a
sensor fails to report properly to the FACP, a “Self-Test Abnormal” condition
occurs. Since the sensor is not working properly, it must be replaced. Replace
it, or call your local branch office for service.
Expired The FACP panel generates an Expired trouble to notify the user that a
replacement sensor is required. To clear the trouble, a new CRS with a valid
date must be installed, and a hardware reset of the FACP panel must be
performed.
Trouble Indications
Trouble Indications
for TrueAlarm
Sensors
Continued on next page
5-10
Table 5-5. Sensor’s Analog Value
Trouble Indications,
Continued
The panel will automatically indicate when a sensor is out of its sensitivity calibration. If
the sensor has an analog value below what is listed in the table, the sensor is within its
sensitivity setting.
Sensor’s Analog Value
Type Almost Dirty Dirty Excessively Dirty
Photo 115 120 135
Ion 135 140 155
To view a Sensor’s analog value, refer to your panels operating instructions
5-11
Date Time Event/Description Initials
Fire Alarm Trouble and Maintenance Log
Fire Alarm
Trouble and
Maintenance Log
1
2
2120 CDT System
address setting, 3-5
2-Wire Relay Base Connections, 2-12
4
4010 System
address setting, 3-5
4020 System
address setting, 3-5
4100+ System
address setting, 3-5
4100U/ 4100ES System
address setting, 3-5
4120 System
address setting, 3-5
4-Wire Base Connections, 2-13
A
Accessories, 4-1
Authorities Having Jurisdiction, 2-2
B
Base compatibility, 5-2
Bases
4098, 2-8
wiring, 2-10
C
Cautions and Warnings, iv
Cleaning, 5-8
CO Sensor Bases, 1-8
CRS, replacing, 3-10, 3-11
Common Code Requirements, 2-8
Compatibility, 5-1
Copyrights, iii
CRS
replacing, 3-10, 3-11
D
Detector compatibility, 5-2
Detectors
placement, 1-5
Wall and Ceiling Mounted, 1-4
where not to place, 1-6
where to place, 1-3
E
Environmental conditions, 1-6
H
Heat Detectors
4098, 2-5
fixed temperature, 2-5
LED Base Connections, 2-14
models, 2-6
ROR Temperature, 2-5
specifications, 2-6
types, 2-5
HVAC Systems, 1-3
I
IDNet Addresses, 3-6
Ionization Detectors
testing, 5-7
Isolator Sensor Bases
connections, 3-9
M
Magnetic Test, 5-5
Maintenance, 5-4
MAPNET Addresses, 3-6
Mulit-Sensor Bases
DIP Switch settings, 3-7
Multi-Sensor Bases, 3-7
N
NFPA 70, 1-3
NFPA 72, 1-2, 1-3, 1-4, 2-2, 2-8, 3-1
NFPA 90A, 1-3
O
Operation
principles of, 1-8
P
Photoelectric Detectors
testing, 5-5
Programmer reports, 3-5
Q
QuickConnect Smoke Sensors, 3-12
DIP Switch settings, 3-13
specifications, 3-12
R
Rate-of-rise, 1-8
Relay module
2098-9737 wiring, 4-2
4098-9822 wiring, 4-3
accessories, 4-1
installation, 4-4
Remote LED module, 4-4
S
Sensor base compatibility,
5-3
Sensor Compatibility,
5-3
Sensors
Wall and Ceiling Mounted, 1-4
where not to place, 1-6
where to place, 1-3
Smoke Detector Application, 1-2
Smoke Detectors
4098, 2-2
limitations, 2-2
mounting, 2-4
photoelectric, 1-8
specifications, 2-3
Smoke Sensor Application, 1-2
Smoke Sensors
photoelectric, 1-8
Style B or D Initiating Circuits, 2-11
T
Test Equipment, 5-4
Testing, 5-4
detectors and sensors, 5-4
thermistors, 1-8
Trademarks, iii
Trouble and Maintenance Log, 5-10
Index
IN-1
2
Trouble Indications, 5-9
TrueAlarm Concepts, 1-8
TrueAlarm QuickConnect Smoke Sensors,
3-12
TrueAlarm Sensor Bases
4098, 3-3
setting the address, 3-4
specifications, 3-3
wiring,
3-8
TrueAlarm Sensors
DIP Switch location, 3-4
special applications, 3-2
TrueAlarm Sensors, mounting, 3-2
IN-2
4
574-709
Rev. T
© 2008-2011 SimplexGrinnell LP. Specifications and other information were current as of publication and are subject to change without notice.